Decentral Solutions
Bit
Bit = 0
Bit =1
00
OFF 1
ON 1
01
OFF 2
ON 2
02
OFF 3
ON 3
03
Coasting stop
04
Quick stop
05
Freeze outp. freq.
06
Ramp stop
Start
07
Reset
08
Bus jog 1
09
Bus jog 2
10
Data not valid
Data valid
11
Slow down
12
Catch-up
13
Select Setup (lsb)
14
Select Setup (msb)
15
Reverse
Bit 00-01-02, OFF1-2-3/ON1-2-3:
Bit 00-01-02 =
’
0
’
causes ramp stop, which uses the
ramp time in parameters 207/208 or 209/210.
If
Relay 123
is selected in parameter 323
Relay
output
, the output relay will be activated when
the output frequency is 0 Hz.
Bit 00-01-02 =
’
1
’
means that the variable
frequency drive can start the motor if the other
starting conditions are fulfilled.
Bit 03, Coasting stop:
See description under
Control word according
to FC protocol.
Bit 04, Quick stop:
See description under
Control word according
to FC protocol.
Bit 05, Freeze output frequency:
See description under
Control word according
to FC protocol.
Bit 06, Ramp stop/start:
See description under
Control word according
to FC protocol.
Bit 07, Reset:
See description under
Control word according
to FC protocol.
Bit 08, Jog 1:
Bit 08 = "1" means that the output frequency is
determined by parameter 09
Bus jog 1
.
Bit 09, Jog 2:
Bit 09 = "1" means that the output frequency is
determined by parameter 510
Bus jog 2
.
Bit 10, Data not valid/Data valid:
See description under
Control word according
to FC protocol.
Bit 11, Slow-down:
Used to reduce the speed reference by the value in
parameter 219
Catch-up/slow-down reference
.
Bit 11 =
’
0
’
does not cause any change to the reference.
Bit 11 =
’
1
’
means that the reference is reduced.
Bit 12, Catch-up:
Used to increase the speed reference by the value in
parameter 219
Catch-up/slow-down reference
.
Bit 12 =
’
0
’
does not cause any change to the reference.
Bit 12 =
’
1
’
means that the reference is increased.
If both
Slow down
and
Catch-up
are activated (Bits
11 and 12 = "1"), slow down has the highest priority,
i.e. that the speed reference is reduced.
Bit 13/14, Selection of Setup:
See description under
Control word according
to FC protocol.
Bit 15 Reverse:
See description under
Control word according
to FC protocol.
■
Status word according to Profidrive protocol
The status word is used to inform the master
(e.g. a PC) of the slave
’
s (variable frequency
drive) mode. Slave
Master.
MG.90.F2.22 - VLT is a registered Danfoss trademark
158
Содержание VLT Decentral FCD 300
Страница 28: ...Decentral Solutions Ordering form FCD 300 MG 90 F2 22 VLT is a registered Danfoss trademark 28 ...
Страница 48: ...Decentral Solutions Electrical Schematic MG 90 F2 22 VLT is a registered Danfoss trademark 48 ...
Страница 178: ...Decentral Solutions Dimensions of mounting brackets MG 90 F2 22 VLT is a registered Danfoss trademark 178 ...