
130BB838.12
a
b
c
d
e
f
A
Installations with cables connected in a common joint as shown in A and B are only recommended for short cable lengths.
B
Be aware of the maximum motor cable length specified in
chapter 5.5 Cable Specifications
.
C
The total motor cable length specified in
chapter 5.5 Cable Specifications
is valid as long as the parallel cables are kept less than
10 m (32 ft) each.
D
Consider voltage drop across the motor cables.
E
Consider voltage drop across the motor cables.
F
The total motor cable length specified in
chapter 5.5 Cable Specifications
is valid as long as the parallel cables are kept less than
10 m (32 ft) each.
Illustration 7.10 Different Parallel Connections of Motors
Electrical Installation Con...
VLT® AutomationDrive FC 361
46
Danfoss A/S © 03/2019 All rights reserved.
MG06K102
7
7
Содержание VLT AutomationDrive FC 361
Страница 2: ......