3.3 Configure the Frequency Converter
3.3.1 VLT Parameters
The following parameters are important when configuring
the frequency converter with a PROFINET interface:
•
Parameter 0-40 [Hand on] Key on LCP
. If [Hand On]
is activated, control of the frequency converter
via the PROFINET interface is disabled.
•
After an initial power-up, the frequency converter
automatically detects whether a fieldbus option is
installed in slot A and sets
to
[Option A]
. When an option is added,
changed, or removed from an already commis-
sioned frequency converter, it does not change
but enters
Trip
mode, and the frequency converter shows an
error.
•
Parameter 8-10 Control Word Profile
. Select
between the Danfoss frequency converter profile
and the PROFIdrive profile.
•
Parameter 8-50 Coasting Select
to
parameter 8-58 Profidrive OFF3 Select
. Select how
to gate PROFINET control commands with the
digital input command of the control card.
NOTICE
When
parameter 8-01 Control Site
is set to
[2] Control
word only
, the settings from
parameter 8-50 Coasting
Select
to
parameter 8-58 Profidrive OFF3 Select
are
overruled and only act on bus control.