3.3.2 Ordering Numbers: Brake Resistors 40%
FC 360
P
m (HO)
R
min
R
br. nom
R
rec
P
br avg
Code no.
Period
Cable
cross
section
1)
Thermal
relay
Maximum
brake
torque
with R
rec
T4
[kW]
[
Ω
]
[
Ω
]
[
Ω
]
[kW]
175Uxxxx
[s]
[mm
2
]
[A]
[%]
HK37
0.37
890
1041.98
989
0.127
3101
120
1.5
0.4
139
HK55
0.55
593
693.79
659
0.191
3308
120
1.5
0.5
131
HK75
0.75
434
508.78
483
0.260
3309
120
1.5
0.7
129
H1K1
1.1
288
338.05
321
0.391
3310
120
1.5
1
132
H1K5
1.5
208
244.41
232
0.541
3311
120
1.5
1.4
145
H2K2
2.2
139
163.95
155
0.807
3312
120
1.5
2.1
131
H3K0
3
100
118.86
112
1.113
3313
120
1.5
2.7
131
H4K0
4
74
87.93
83
1.504
3314
120
1.5
3.7
128
H5K5
5.5
54
63.33
60
2.088
3315
120
1.5
5
127
H7K5
7.5
38
46.05
43
2.872
3316
120
1.5
7.1
132
H11K
11
27
32.99
31
4.226
3236
120
2.5
11.5
130
H15K
15
19
24.02
22
5.804
3237
120
2.5
14.7
129
H18K
18.5
16
19.36
18
7.201
3238
120
4
19
132
H22K
22
16
18.00
17
8.604
3203
120
4
23
128
H30K
30
11
14.6
13
11.5
3206
120
10
32
150
H37K
37
9
11.7
11
14.3
3210
120
10
38
150
H45K
45
8
9.6
9
17.5
3213
120
16
47
150
H55K
55
6
7.8
7
21.5
3216
120
25
61
150
H75K
75
4
5.7
5
29.6
3219
120
35
81
150
Table 3.3 FC 360 - Mains: 380–480 V (T4), 40% Duty Cycle
1) All cabling must comply with national and local regulations on cable cross-sections and ambient temperature.
Type Code and Selection
Design Guide
MG06B402
Danfoss A/S © 09/2014 All rights reserved.