an equalizing cable next to the control cable. Minimum
cable cross-section: 16 mm
2
.
Min. 16 mm²
PE
FC
PE
PLC
130BB922.10
PE
PE
- Equalizing cable
50/60Hz ground loops
With very long control cables, ground loops may occur. To
eliminate ground loops, connect one end of the shield-to-
ground with a 100nF capacitor (keeping leads short).
100nF
FC
PE
PE
PLC
130BB609.11
Avoid EMC noise on serial communication
This terminal is grounded via an internal RC link. Use
twisted-pair cables to reduce interference between
conductors. The recommended method is shown below:
Min. 16 mm²
PE
FC
PE
FC
130BB923.10
PE
PE
- Equalizing cable
69
68
61
69
68
61
Alternatively, the connection to terminal 61 can be
omitted:
Min. 16 mm²
PE
FC
PE
FC
130BB924.10
PE
PE
- Equalizing cable
69
69
68
68
2.4.5.5 Control Terminal Functions
Adjustable frequency drive functions are commanded by
receiving control input signals.
•
Each terminal must be programmed for the
function it will be supporting in the parameters
associated with that terminal. See
for
terminals and associated parameters.
•
It is important to confirm that the control
terminal is programmed for the correct function.
See
for details on accessing
parameters and
for details on programming.
•
The default terminal programming is intended to
initiate Adjustable frequency drive functioning in
a typical operational mode.
2.4.5.6 Jumper Terminals 12 and 27
A jumper wire may be required between terminal 12 (or
13) and terminal 27 for the Adjustable frequency drive to
operate when using factory default programming values.
•
Digital input terminal 27 is designed to receive an
24V DC external interlock command. In many
applications, the user wires an external interlock
device to terminal 27.
•
When no interlock device is used, wire a jumper
between control terminal 12 (recommended) or
13 to terminal 27. This provides an internal 24V
signal on terminal 27
•
No signal present prevents the unit from
operating.
•
When the status line at the bottom of the LCP
reads AUTO REMOTE COAST, this indicates that
the unit is ready to operate but is missing an
input signal on terminal 27.
•
When factory installed optional equipment is
wired to terminal 27, do not remove that wiring.
2.4.5.7 Terminal 53 and 54 Switches
•
Analog input terminals 53 and 54 can select
either voltage (-10–10V) or current (0/4–20mA)
input signals
•
Remove power to the Adjustable frequency drive
before changing switch positions
•
Set switches A53 and A54 to select the signal
type. U selects voltage, I selects current.
•
The switches are accessible when the LCP has
been removed (see
). Note that some
option cards available for the unit may cover
these switches and must be removed to change
switch settings. Always remove power to the unit
before removing option cards.
•
Terminal 53 default is for a speed reference signal
in open-loop set in
16-61 Terminal 53 Switch
Setting
•
Terminal 54 default is for a feedback signal in
closed-loop set in
16-63 Terminal 54 Switch Setting
Installation
VLT
®
AutomationDrive Instruction
Manual
2-10
MG.33.AI.22 - VLT
®
is a registered Danfoss trademark
2
2
Содержание VLT AutomationDrive FC 303
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual VLT AutomationDrive FC 300...
Страница 3: ...Safety VLT AutomationDrive Instruction Manual MG 33 AI 22 VLT is a registered Danfoss trademark...
Страница 7: ...Contents VLT AutomationDrive Instruction Manual MG 33 AI 22 VLT is a registered Danfoss trademark...
Страница 13: ...Introduction VLT AutomationDrive Instruction Manual 1 6 MG 33 AI 22 VLT is a registered Danfoss trademark 1 1...
Страница 29: ...Installation VLT AutomationDrive Instruction Manual 2 16 MG 33 AI 22 VLT is a registered Danfoss trademark 2 2...
Страница 101: ...Specifications VLT AutomationDrive Instruction Manual 10 26 MG 33 AI 22 VLT is a registered Danfoss trademark 10 10...
Страница 105: ...www danfoss com drives MG33AI22 130R0300 MG33AI22 Rev 2011 05 13...