8-17 Configurable Alarm and Warningword
The configurable alarm and warning word has 16 bits (0–15).
Each of those bits can be configured to any of the following
options.
Option:
Function:
[10073]
Safestop auto restart alarm
[10074]
PTC thermistor alarm
[10075]
Illegal profile alarm
[10078]
Tracking error alarm
[10079]
Illegal PS config alarm
[10081]
CSIV corrupt alarm
[10082]
CSIV param error alarm
[10084]
No safety option alarm
[10090]
Feedback monitor alarm
[10091]
AI54 settings alarm
[10164]
ATEX ETR current lim alarm
[10166]
ATEX ETR freq limit alarm
8-19 Product Code
Range:
Function:
Size
related
*
[0 -
2147483647 ]
Select 0 to read out the actual
fieldbus product code according
to the mounted fieldbus option.
Select 1 to read out the actual
vendor ID.
3.9.3 8-3* FC Port Settings
8-30 Protocol
Option:
Function:
Select the protocol to be used. Changing
protocol is not effective until after powering
off the frequency converter.
[0]
*
FC
[1]
FC MC
[2]
Modbus RTU
8-31 Address
Range:
Function:
1
*
[ 1 - 247 ] Enter the address for the frequency converter
(standard) port.
Valid range: Depends on selected protocol.
8-32 FC Port Baud Rate
Option:
Function:
[0] 2400 Baud
Baud rate selection for the FC (standard) port.
[1] 4800 Baud
[2] 9600 Baud
[3] 19200 Baud
[4] 38400 Baud
[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
8-33 Parity / Stop Bits
Option:
Function:
[0]
*
Even Parity, 1 Stop Bit
[1]
Odd Parity, 1 Stop Bit
[2]
No Parity, 1 Stop Bit
[3]
No Parity, 2 Stop Bits
8-34 Estimated cycle time
Range:
Function:
0 ms
*
[0 -
1000000 ms]
In noisy environments, the interface may
be blocked due to overload or bad frames.
This parameter specifies the time between
2 consecutive frames on the network. If the
interface does not detect valid frames in
that time, it flushes the receive buffer.
8-35 Minimum Response Delay
Range:
Function:
10 ms
*
[ 1 - 10000
ms]
Specify the minimum delay time
between receiving a request and
transmitting a response. This is used for
overcoming modem turnaround delays.
8-36 Max Response Delay
Range:
Function:
Size
related
*
[ 11 -
10001 ms]
Specify the maximum allowed delay
time between transmitting a request
and receiving a response. If a response
from the frequency converter is
exceeding the time setting, then it is
discarded.
8-37 Max Inter-Char Delay
Range:
Function:
Size
related
*
[ 0.00 -
35.00 ms]
Specify the maximum allowed time
interval between receipt of 2 bytes. This
parameter activates timeout if
transmission is interrupted.
This parameter is active only when
parameter 8-30 Protocol
is set to
[1] FC MC
protocol.
3.9.4 8-4* FC MC Protocol Set
8-40 Telegram Selection
Option:
Function:
[1]
*
Standard telegram 1 Enables use of freely configurable
telegrams or standard telegrams for
the FC port.
[100] None
[101] PPO 1
[102] PPO 2
[103] PPO 3
[104] PPO 4
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
160
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
3
3