3-02 Minimum Reference
Range:
Function:
for
[1] Speed closed loop
,
RPM; for
[2] Torque
, Nm.
•
The unit selected in
3-01 Reference/Feedback
Unit
.
3-03 Maximum Reference
Range:
Function:
Size
related
*
[ par. 3-02 -
999999.999
ReferenceFeed-
backUnit]
Enter the Maximum Reference. The
Maximum Reference is the highest
value obtainable by summing all
references.
The Maximum Reference unit
matches:
•
The choice of configu-
ration in
1-00 Configuration Mode
:
for
[1] Speed closed loop
,
RPM; for
[2] Torque
, Nm.
•
The unit selected in
3-00 Reference Range
.
3-41 Ramp 1 Ramp Up Time
Range:
Function:
Size
related
*
[ 0.01
- 3600
s]
Enter the ramp-up time, i.e. the acceleration
time from 0 RPM to the synchronous motor
speed n
S
. Select a ramp-up time such that
the output current does not exceed the
current limit in
4-18 Current Limit
during
ramping. The value 0.00 corresponds to 0.01
s in speed mode. See ramp-down time in
parameter 3-42 Ramp 1 Ramp Down Time
Par. 3−41 = tacc s x ns RPM
ref RPM
3-42 Ramp 1 Ramp Down Time
Range:
Function:
Size
related
*
[ 0.01 -
3600 s]
Enter the ramp-down time, that is, the
deceleration time from the synchronous
motor speed n
s
to 0 RPM. Select a ramp-
down time such that no overvoltage arises
in the inverter due to regenerative
operation of the motor, and such that the
generated current does not exceed the
current limit set in
4-18 Current Limit
. The
value 0.00 corresponds to 0.01 s in speed
mode. See ramp-up time in
parameter 3-41 Ramp 1 Ramp Up Time
Par. 3−42 = tdec s x ns RPM
ref RPM
4.3 Parameter Menu Structure
How to Programme
VLT
®
Automation Drive FC 300 Operating Instructions
MG33U402 - Rev. 2013-12-16
85
4
4