6.4.7 300-** AF Settings
NOTICE!
Except for
300-10 Active Filter Nominal Voltage
, it is not recommended to change the settings in this parameter group
for the Low Harmonic Drive
Par. No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion index
Type
300-0* General Settings
300-00
Harmonic cancellation mode
[0] Overall
All set-ups
TRUE
-
Uint8
300-01
Compensation priority
[0] Harmonics
All set-ups
TRUE
-
Uint8
300-08
Lagging reactive current
[0] Disabled
All set-ups
FALSE
Uint8
300-1* Network Settings
300-10
Active filter nominal voltage
ExpressionLimit
2 set-ups
FALSE
0
Uint32
300-2* CT Settings
300-20
CT primary rating
ExpressionLimit
2 set-ups
FALSE
0
Uint32
300-24
CT Sequence
[0] L1, L2, L3
2 set-ups
FALSE
-
Uint8
300-25
CT Polarity
[0] Normal
2 set-ups
FALSE
-
Uint8
300-26
CT Placement
[1] Load Current
2 set-ups
FALSE
-
Uint8
300-27
Number of CTs per phase
1
All set-ups
FALSE
Uint8
300-29
Start auto CT detection
[0] Off
All set-ups
FALSE
-
Uint8
300-3* Compensation
300-30
Compensation points
0.0 A
All set-ups
TRUE
-1
Uint32
300-35
Cosphi reference
0.500 N/A
All set-ups
TRUE
-3
Uint16
300-4* Paralleling
300-40
Master follower selection
[2] Not Paralleled
2 set-ups
FALSE
-
Uint8
300-41
Follower ID
1 N/A
2 set-ups
FALSE
0
Uint32
300-42
Num. of follower AFs
1 N/A
2 set-ups
FALSE
0
Uint32
300-5* Sleep Mode
300-50
Enable sleep mode
null
2 set-ups
TRUE
-
Uint8
300-51
Sleep mode trig source
[0] Mains current
All set-ups
TRUE
-
Uint8
300-52
Sleep mode wake up trigger
ExpressionLimit
All set-ups
TRUE
0
Uint32
300-53
Sleep mode sleep trigger
80 %
All set-ups
TRUE
0
Uint32
Programming
Instruction Manual
MG37A222
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
117
6
6