6.4.3 8-** Comm. and Options
Par. No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion index
Type
8-0* General Settings
8-01
Control site
[0] Digital and ctrl.word
All set-ups
TRUE
-
Uint8
8-02
Control word source
null
All set-ups
TRUE
-
Uint8
8-03
Control word timeout time
1.0 s
1 set-up
TRUE
-1
Uint32
8-04
Control word timeout function
[0] Off
1 set-up
TRUE
-
Uint8
8-05
End-of-timeout function
[1] Resume set-up
1 set-up
TRUE
-
Uint8
8-06
Reset control word timeout
[0] Do not reset
All set-ups
TRUE
-
Uint8
8-3* FC Port Settings
8-30
Protocol
[1] FC MC
1 set-up
TRUE
-
Uint8
8-31
Address
2 N/A
1 set-up
TRUE
0
Uint8
8-32
FC port baud rate
[2] 9600 Baud
1 set-up
TRUE
-
Uint8
8-33
Parity/stop bits
[0] Even parity, [1] Stop
bit
All set-ups
TRUE
Uint8
8-35
Minimum response delay
10 ms
All set-ups
TRUE
-3
Uint16
8-36
Max response delay
5000 ms
1 set-up
TRUE
-3
Uint16
8-37
Max inter-char delay
25 ms
1 set-up
TRUE
-3
Uint16
8-4* FC MC Protocol Set
8-42
PCD write configuration
[1685] FC port CTW 1
All set-ups
TRUE
Uint16
8-43
PCD read configuration
[1603] Status word
All set-ups
TRUE
Uint16
8-5* Digital/Bus
8-53
Start select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-55
Set-up select
[3] Logic OR
All set-ups
TRUE
-
Uint8
Programming
Instruction Manual
112
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
MG37A222
6
6