a.
-
b.
-
c.
-
d.
2.
-
-
-
Parameter 1-23 Motor Frequency
.
Parameter 1-24 Motor Current
.
Parameter 1-25 Motor Nominal Speed
.
Parameter 1-26 Motor Cont. Rated Torque
.
Run a complete AMA.
Select
[1] Enable Complete AMA
in
parameter 1-29 Automatic Motor Adaptation (AMA)
, or
Enter the following manually:
Parameter 1-30 Stator Resistance (Rs)
.
Parameter 1-37 d-axis Inductance (Ld)
.
Parameter 1-44 d-axis Inductance Sat. (LdSat)
.
Parameter 1-45 q-axis Inductance Sat. (LqSat)
.
Parameter 1-48 Inductance Sat. Point
.
5.2.2.3.3 Application-specific Adjustment when Running VVC+ with SynRM Motors
Start the motor at nominal speed. If the application does not run well, check the VVC+ SynRM settings.
Application
Settings
Low-inertia applications
I
Load
/I
Motor
<5
Increase
parameter 1-17 Voltage filter time const.
by factor 5–10.
Reduce
parameter 1-14 Damping Gain
.
Reduce
parameter 1-66 Min. Current at Low Speed
(<100%).
Low-inertia applications
50>I
Load
/I
Motor
>5
Keep the default values.
High-inertia applications
I
Load
/I
Motor
>50
Increase
parameter 1-14 Damping Gain
,
parameter 1-15 Low Speed Filter Time Const.
, and
parameter
1-16 High Speed Filter Time Const
.
High-load at low speed
<30% (rated speed)
Increase
parameter 1-17 Voltage filter time const
. Increase
parameter 1-66 Min. Current at Low Speed
to adjust the starting torque. 100% current provides nominal torque as starting torque. Working
at a current level higher than 100% for a prolonged time can cause the motor to overheat.
Dynamic applications
Increase
parameter 14-41 AEO Minimum Magnetisation
for highly dynamic applications. Adjusting
parameter 14-41 AEO Minimum Magnetisation
ensures a good balance between energy efficiency
and dynamics. Adjust
parameter 14-42 Minimum AEO Frequency
to specify the minimum frequen-
cy at which the drive should use minimum magnetization.
Motor sizes less than 18 kW
(24 hp)
Avoid short ramp-down times.
If the motor starts oscillating at a certain speed, increase
parameter 1-14 Damping Gain
. Increase the damping gain value in small
steps. Depending on the motor, this parameter can be set to 10–100% higher than the default value.
5.2.3 1-1* Special Settings
N O T I C E
The following parameter is only available in FC 302:
Parameter 1-11 Motor Model
N O T I C E
The parameters within this parameter group cannot be adjusted while the motor is running.
AU275636650261en-000101 / 130R0334
72 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide