Enter the current (mA) that corresponds to the high reference value set in
parameter 35-45 Term. X48/2 High Ref./Feedb. Value
.
Parameter 35-44 Term. 48/2 Low Ref./Feedb. Value
Table 1300: Parameter 35-44 Term. 48/2 Low Ref./Feedb. Value
35-44 Term. 48/2 Low Ref./Feedb. Value
Default value: 0 ReferenceFeedbackUnit Parameter type: Range, -999999.999 - 999999.999
ReferenceFeedbackUnit
Setup: All setups
Conversion index: 0
Data type: Int32
Change during operation: True
Enter the reference or feedback value (in RPM, Hz, bar, and so on) that corresponds to the voltage or current set in
parameter 35-42
Term. X48/2 Low Current
.
Parameter 35-45 Term. 48/2 High Ref./Feedb. Value
Table 1301: Parameter 35-45 Term. 48/2 High Ref./Feedb. Value
35-45 Term. 48/2 High Ref./Feedb. Value
Default value: 100 ReferenceFeedbackU-
nit
Parameter type: Range, -999999.999 - 999999.999
ReferenceFeedbackUnit
Setup: All setups
Conversion index: 0
Data type: Int32
Change during operation: True
Enter the reference or feedback value (in RPM, Hz, bar, and so on) that corresponds to the voltage or current set in
parameter 35-43
Term. X48/2 High Current
.
Parameter 35-46 Term. X48/2 Filter Time Constant
Table 1302: Parameter 35-46 Term. X48/2 Filter Time Constant
35-46 Term. X48/2 Filter Time Constant
Default value: 0.001 s
Parameter type: Range, 0.001 - 10 s
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: True
Enter the filter time constant. This is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal
X48/2. A high time constant value improves dampening but also increases the time delay through the filter.
5.29 Parameter Group 36-** Programmable I/O Option
Parameters for configuring VLT® Programmable I/O MCB 115.
Parameters in this group are only active if VLT® Programmable I/O MCB 115 is installed.
5.29.1 36-0* I/O Mode
N O T I C E
The following parameters are only available in FC 302:
Parameter 36-00 Terminal X49/1 Mode
Parameter 36-01 Terminal X49/3 Mode
Parameter 36-02 Terminal X49/5 Mode
Parameter 36-00 Term. X49/1 Mode
Table 1303: Parameter 36-00 Term. X49/1 Mode
36-00 Term. X49/1 Mode
Default value: [1] Voltage
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: True
AU275636650261en-000101 / 130R0334
636 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide