5.28.3 35-2* Temp. Input X48/7
Table 1290: Parameter 35-24 Term. X48/7 Filter Time Constant
35-24 Term. X48/7 Filter Time Constant
Default value: 0.001 s
Parameter type: Range, 0.001 - 10 s
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: True
Enter the filter time constant. This is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal
X48/7. A high time constant value improves dampening but also increases the time delay through the filter.
Parameter 35-25 Term. X48/7 Temp. Monitor
Table 1291: Parameter 35-25 Term. X48/7 Temp. Monitor
35-25 Term. X48/7 Temp. Monitor
Default value: [0] Disabled
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: True
This parameter facilitates the possibility of enabling or disabling the temperature monitor for terminal X48/4. Set the temperature
limits in
parameter 35-26 Term. X48/7 Low Temp. Limit
and
parameter 35-27 Term. X48/7 High Temp. Limit
.
Option
Name
Description
[0]*
Disabled
[1]
Enabled
Parameter 35-26 Term. X48/7 Low Temp. Limit
Table 1292: Parameter 35-26 Term. X48/7 Low Temp. Limit
35-26 Term. X48/7 Low Temp. Limit
Default value: Size related
Parameter type: Range, N/A
Setup: All setups
Conversion index: 0
Data type: Int16
Change during operation: True
Enter the minimum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/7.
Parameter 35-27 Term. X48/7 High Temp. Limit
Table 1293: Parameter 35-27 Term. X48/7 High Temp. Limit
35-27 Term. X48/7 High Temp. Limit
Default value: Size related
Parameter type: Range, N/A
Setup: All setups
Conversion index: 0
Data type: Int16
Change during operation: True
Enter the maximum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/7.
5.28.4 35-3* Temp. Input X48/10
Parameter 35-34 Term. X48/10 Filter Time Constant
Table 1294: Parameter 35-34 Term. X48/10 Filter Time Constant
35-34 Term. X48/10 Filter Time Constant
Default value: 0.001 s
Parameter type: Range, 0.001 - 10 s
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: True