0-13 Readout: Linked Set-ups
Array [5]
Range:
Function:
0
*
[0 -
255 ]
View a list of all the set-ups linked by means of
0-12 This
Set-up Linked to
. The parameter has one index for each
parameter set-up. The parameter value displayed for
each index represents which setups are linked to that
parameter setup.
Index
LCP value
0
{0}
1
{1,2}
2
{1,2}
3
{3}
4
{4}
Table 3.2 Example: Set-up 1 and Set-up 2 are linked
0-14 Readout: Edit Set-ups / Channel
Range:
Function:
0
*
[-2147483648 -
2147483647 ]
View the setting of
for each
of the four different communication
channels. When the number is displayed in
hex, as it is in the LCP, each number
represents one channel.
Numbers 1-4 represent a set-up number; ‘F’
means factory setting; and ‘A’ means active
set-up. The channels are, from right to left:
LCP, FC-bus, USB, HPFB1-5.
Example: The number AAAAAA21h means
that the FC bus selected Set-up 2 in
, the LCP selected Set-up 1 and all
others used the active set-up.
3.2.3 0-2* LCP Display
Define the variables displayed in the Graphical Local Control
Panel.
NOTE
Please refer to
0-37 Display Text 1
,
0-38 Display Text 2
and
0-39 Display Text 3
for information on how to write display
texts.
0-20 Display Line 1.1 Small
Option:
Function:
Select a variable for display in line
1, left position.
[0]
*
None
No display value selected.
[9]
Performance Monitor
[37]
Display Text 1
[38]
Display Text 2
[39]
Display Text 3
[748]
PCD Feed Forward
[953]
Profibus Warning
Word
[1005]
Readout Transmit
Error Counter
[1006]
Readout Receive Error
Counter
[1007]
Readout Bus Off
Counter
[1013]
Warning Parameter
[1230]
Warning Parameter
[1472]
Legacy Alarm Word
[1473]
Legacy Warning Word
[1474]
Leg. Ext. Status Word
[1501]
Running Hours
[1502]
kWh Counter
[1600]
Control Word
Present control word
[1601]
Reference [Unit]
Total reference (sum of digital/
analog/preset/bus/freeze ref./
catch up and slow-down) in
selected unit.
[1602]
Reference %
Total reference (sum of digital/
analog/preset/bus/freeze ref./
catch up and slow-down) in
percent.
[1603]
Status Word
Present status word.
[1605]
Main Actual Value [%] Actual value as a percentage.
[1609]
Custom Readout
[1610]
Power [kW]
Actual power consumed by the
motor in kW.
[1611]
Power [hp]
Actual power consumed by the
motor in HP.
Parameter Descriptions
FC 300 Programming Guide
26