FC 300 Operating Instructions
How to Programme
Basic Parameters
0-01 Language
Option:
*
English (ENGLISH)
[0]
German (DEUTSCH)
[1]
French (FRANCAIS)
[2]
Danish (DANSK)
[3]
Spanish (ESPANOL)
[4]
Italian (ITALIANO)
[5]
Chinese (CHINESE)
[10]
Function:
Choose the desired LCP language.
1-20 Motor Power [kW]
Range:
0.37-7.5 kW
[Motor
type de-
pendent]
Function:
The value should equal the nameplate data on the
connected motor. The default value corresponds to
the nominal rated output of the unit.
NB!:
Changing the value in this parameter
affects the setting of other parameters.
Par. 1-20 cannot be changed while the
motor is running.
1-22 Motor Voltage
Range:
200-600 V
[Motor
type de-
pendent]
Function:
The value should equal the nameplate data on the
connected motor. The default value corresponds to
the nominal rated output of the unit.
NB!:
Changing the value in this parameter
affects the setting of other parameters.
Par. 1-22 cannot be changed while the
motor is running.
1-23 Motor Frequency
Option:
*
50 Hz (50 HZ)
[50]
60 Hz (60 HZ)
[60]
Min - Max motor frequency: 20 - 300 Hz [60]
Function:
Select the stated value from the motor name plate.
Alternatively, set the value for motor frequency to
be infinitely variable. If a value different from 50 Hz
or 60 Hz is selected, it is necessary to correct par.
1-50 to 1-54. For 87 Hz operation with 230/400 V
motors, set the nameplate data for 230 V/50 Hz.
Adapt par. 2-02
Output Speed High Limit
and par.
2-05
Maximum Reference
to the 87 Hz application.
NB!:
Changing the value in this parameter
affects the setting of other parameters.
Par. 1-23 cannot be changed while the
motor is running.
NB!:
If a delta connection is used, select
the rated motor frequency for the delta
connection.
1-24 Motor current
Range:
Motor type dependent.
[60]
Function:
The value should equal the nameplate data on
the connected motor. Data is used for calculating
torque, motor protection etc.
NB!:
Changing the value in this parameter
affects the setting of other parameters.
Par. 1-24 cannot be changed while the
motor is running.
1-25 Motor nominal speed
Range:
100. - 60000. RPM
*
RPM
Function:
The value should equal the name plate data on the
connected motor. The data is used for calculating
motor compensations.
1-29 Automatic Motor Adaptation, (AMA)
Option:
*
OFF
[0]
Enable complete AMA
[1]
Enable reduced AMA
[2]
Function:
If the AMA function is used, the frequency converter
automatically sets the necessary control parameters
(par. 1-30 to par. 1-35) with the motor stationary.
*
default setting
( )
display text
[ ]
value for use in communication via serial communication port
32