FC 300 Operating Instructions
How to Programme
Connection Examples
Start/Stop
Terminal 18 = start/stop
Terminal 37 = coasting stop (safe)
Terminal 27 = coast inverse
Par. 5-10
Digital input
=
Start
(default)
Par. 5-12
Digital input
=
coast inverse
(default)
Pulse Start/Stop
Terminal 18 = latched start
Terminal 27= stop inverse
Par. 5-10
Digital input
=
Latched start
Par. 5-12
Digital input
=
Stop inverse
Speed Up/Down
Terminals 29/32 = Speed up/down.
Par. 5-10
Digital Input
=
Start
(default)
Par. 5-12
Digital input
=
Freeze reference
Par. 5-13
Digital input
=
Speed up
Par. 5-14
Digital input
=
Speed down
Potentiometer reference
Voltage reference via a potentiometer.
Par. 3-15
Reference resource 1
=
Analog input
53
(default)
Par. 6-10
Terminal 53, low voltage
= 0 Volt
(default)
Par. 6-11
Terminal 53, high voltage
= 10 Volt
(default)
Par. 6-14
Terminal 53, low ref./feedb. value
= 0 RPM (default)
Par. 6-15
Terminal 53, high ref./feedb. value
= 1.500 RPM
Switch S201 = OFF (U)
31