No.
Description
Warning
Alarm/Trip
Alarm/Trip Lock
Parameter Reference
75
Illegal Profile Sel.
X
76
Power Unit Setup
X
77
Reduced Power Mode
X
14-59 Actual Number of
Inverter Units
78
Tracking Error
(X)
(X)
4-34 Tracking Error Function
79
Illegal PS config
X
X
80
Drive Initialized to Default Value
X
81
CSIV corrupt
X
82
CSIV parameter error
X
83
Illegal Option Combination
X
84
No Safety Option
X
88
Option Detection
X
89
Mechanical Brake Sliding
X
90
Feedback Monitor
(X)
(X)
17-61 Feedback Signal
Monitoring
91
Analog input 54 wrong settings
X
S202
104
Mixing Fan Fault
X
X
14-53
163
ATEX ETR cur.lim.warning
X
164
ATEX ETR cur.lim.alarm
X
165
ATEX ETR freq.lim.warning
X
166
ATEX ETR freq.lim.alarm
X
243
Brake IGBT
X
X
X
244
Heatsink temp.
X
X
X
245
Heatsink sensor
X
X
Parameter group 0-7*
246
Pwr.card supply
X
249
Rect. low temp.
X
250
New spare parts
X
251
New Type Code
X
X
Table 8.2 Alarm/Warning Code List
(X) Dependent on parameter
1)
Cannot be Auto reset via 14-20 Reset Mode
8.5 Fault Messages
The warning/alarm information below defines each
warning/alarm condition, provides the probable cause for
the condition, and details a remedy or troubleshooting
procedure.
WARNING 1, 10 Volts low
The control card voltage is below 10 V from terminal 50.
Remove some of the load from terminal 50, as the 10 V
supply is overloaded. Max. 15 mA or minimum 590
Ω
.
This condition can be caused by a short in a connected
potentiometer or improper wiring of the potentiometer.
Troubleshooting
Remove the wiring from terminal 50. If the warning clears,
the problem is with the customer wiring. If the warning
does not clear, replace the control card.
WARNING/ALARM 2, Live zero error
This warning or alarm only appears if programmed by the
user in
6-01 Live Zero Timeout Function
. The signal on one
of the analog inputs is less than 50% of the minimum
value programmed for that input. Broken wiring or faulty
device sending the signal can cause this condition.
Troubleshooting
Check connections on all the analog input
terminals. Control card terminals 53 and 54 for
signals, terminal 55 common. MCB 101 terminals
11 and 12 for signals, terminal 10 common. MCB
Warnings and Alarms
VLT
®
Automation Drive D-Frame
Instruction Manual
8-4
MG34U222 - VLT
®
is a registered Danfoss trademark
8
8
Содержание VLT AutomationDrive FC 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual 90 kW 315 kW D frame VLT AutomationDrive FC 300...
Страница 2: ......
Страница 4: ...Safety VLT Automation Drive D Frame Instruction Manual MG34U222 VLT is a registered Danfoss trademark...
Страница 98: ...www danfoss com drives MG34U222 130R0291 MG34U222 Rev 2012 11 15...