Number Description
Warning Alarm/trip Alarm/trip
lock
Parameter reference
215
Start fwd/rev
X
X
–
Parameter 4-74 Start Fwd/Rev Func-
tion
216
Touch timeout
–
X
–
Parameter 4-75 Touch Timout
220
Configuration File Version not suppor-
ted
X
–
–
–
246
Power card supply
–
–
X
–
250
New spare part
–
–
X
–
251
New type code
–
X
X
–
430
PWM disabled
–
X
–
–
1
Cannot be auto reset via
parameter 14-20 Reset Mode
.
(X) Dependent on parameter.
A trip is the action following an alarm. The trip coasts the motor and is reset by pressing [Reset] or by a digital input (
parameter
group 5-1* Digital Inputs
). The original event that caused an alarm cannot damage the drive or cause dangerous conditions.
A trip lock is an action when an alarm occurs, which could damage the drive or connected parts. A trip lock situation can only be
reset by cycling power.
5.1.3 Indicator Light
Table 755: Indicator Light
Warning
Yellow
Alarm
Flashing red
Trip locked
Yellow and red
5.1.4 Alarm Word, Warning Word, and Extended Status Word
Table 756: Description of Alarm Word, Warning Word, and Extended Status Word
Bit Hex
Dec
Alarm word
Alarm word
2
Warning word
Warning
word 2
Extended status word
Alarm Word Extended Status Word
0
00000001 1
Brake check
(A28)
Servicetrip,
read/ write
Brake check
(W28)
Start de-
layed
Ramping
1
00000002 2
Pwr.card temp
(A69)
Servicetrip,
(reserved)
Pwr.card temp
(A69)
Stop de-
layed
AMA running
2
00000004 4
Earth fault
(A14)
Servicetrip,
typecode/
spare part
Earth fault
(W14)
Reserved
Start CW/CCW
start_possible is active, when
the DI selections [12] OR [13]
are active and the requested
direction matches the refer-
ence sign
3
00000008 8
Ctrl.card temp
(A65)
Servicetrip,
(reserved)
Ctrl.card temp
(W65)
Reserved
Slow down
AU373327181955en-000101 / 130R1208 | 353
Danfoss A/S © 2021.08
Troubleshooting
VLT® AutomationDrive EZ FC 321