1-80 Function at Stop
Option:
Function:
1 kW = 0.2 s
10 kW = 0.5 s
100 kW = 1.7 s
1-82 Min Speed for Function at Stop [Hz]
Range:
Function:
0 Hz
*
[0 - 20 Hz] Set the output frequency at which to
activate
parameter 1-80 Function at Stop
.
4.2.10 1-9* Motor Temperature
Parameters for adjusting temperature protection settings
for the motor.
1-90 Motor Thermal Protection
Option:
Function:
[0]
*
No
protection
Continously overloaded motor, when no
warning or trip of the frequency converter is
required.
[1]
Thermistor
warning
Activates a warning when the connected
thermistor or KTY sensor in the motor reacts
in the event of motor overtemperature.
[2]
Thermistor
trip
Stops (trips) the frequency converter when
the connected thermistor or KTY sensor in
the motor reacts in the event of motor
overtemperature.
The thermistor cutout value must be > 3 k
Ω
.
Integrate a thermistor (PTC sensor) in the
motor for winding protection.
[3]
ETR warning
1
Calculates the load when set-up 1 is active,
and activates a warning in the display when
the motor is overloaded. Program a warning
signal via one of the digital outputs.
[4]
ETR trip 1
Calculates the load when set-up 1 is active,
and stops (trips) the frequency converter
when the motor is overloaded. Program a
warning signal via one of the digital outputs.
The signal appears in the event of a warning
and if the frequency converter trips (thermal
warning).
1-93 Thermistor Source
Option:
Function:
NOTICE
This parameter cannot be changed
while the motor is running.
NOTICE
Digital input should be set to
[0] PNP -
Active at 24 V
in
parameter 5-00 Digital
I/O Mode
.
Select the input to which the thermistor
(PTC sensor) should be connected. An
analog input option
[1] Analog Input 53
or
[2] Analog Input 54
cannot be selected if the
analog input is already in use as a reference
source (selected in
parameter 3-16 Reference 2 Source
or
parameter 3-17 Reference 3 Source
[0]
*
None
[1]
Analog Input
53
[2]
Analog Input
54
[3]
Digital input
18
[4]
Digital input
19
[5]
Digital input
32
[6]
Digital input
33
[7]
Digital input
31
Parameter Descriptions
VLT
®
AutomationDrive FC 360
36