21-59 Ext. 3 Output [%]
Range:
Function:
0 %
*
[0 - 100 %] See
parameter 21-19 Ext. 1 Output [%]
for
details.
3.18.7 21-6* Closed Loop 3 PID
21-60 Ext. 3 Normal/Inverse Control
Option:
Function:
See
parameter 21-20 Ext. 1 Normal/Inverse Control
for details.
[0]
*
Normal
[1]
Inverse
21-61 Ext. 3 Proportional Gain
Range:
Function:
0.50
*
[0 - 10 ] See
parameter 21-21 Ext. 1 Proportional Gain
for
details.
21-62 Ext. 3 Integral Time
Range:
Function:
20 s
*
[0.01 - 10000 s] See
parameter 21-22 Ext. 1 Integral Time
for details.
21-63 Ext. 3 Differentation Time
Range:
Function:
0 s
*
[0 - 10 s] See
parameter 21-23 Ext. 1 Differentation Time
for
details.
21-64 Ext. 3 Dif. Gain Limit
Range:
Function:
5
*
[1 - 50 ] See
parameter 21-24 Ext. 1 Dif. Gain Limit
for
details.
21-66 Ext. 3 On Reference Bandwidth
Range:
Function:
5 %
*
[0 - 200 %] Enter the on-reference bandwidth. When the
PID control error (the difference between the
reference and the feedback) is less than the
value of this parameter, the on-reference
status bit is high.
Parameter Description
VLT
®
AQUA Drive FC 202
176
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02
3
3