8 Specifications
8.1 Electrical data
8.1.1 Mains Supply 1x200–240 V AC
Table 25: Mains Supply 1x200–240 V AC, Normal Overload 110% for 1 Minute, P1K1–P22K
Type designation
P1K1
P1K5
P2K2
P3K0
P3K7
P5K5
P7K5
P15K
P22K
Typical shaft output [kW]
1.1
1.5
2.2
3.0
3.7
5.5
7.5
15
22
Typical shaft output at 240 V
[hp]
1.5
2.0
3.0
4.0
5.0
7.5
10
20
30
Protection rating IP20/Chassis
A3
–
–
–
–
–
–
–
–
Protection rating IP21/Type 1
–
B1
B1
B1
B1
B1
B2
C1
C2
Protection rating IP55/Type
12
A5
B1
B1
B1
B1
B1
B2
C1
C2
Protection rating IP66/NEMA
4X
A5
B1
B1
B1
B1
B1
B2
C1
C2
Output current
Continuous (3x200–240 V) [A]
6.6
7.5
10.6
12.5
16.7
24.2
30.8
59.4
88
Intermittent (3x200–240 V)
[A]
7.3
8.3
11.7
13.8
18.4
26.6
33.4
65.3
96.8
Continuous kVA at 208 V [kVA] 2.4
2.7
3.8
4.5
6.0
8.7
11.1
21.4
31.7
Maximum input current
Continuous (1x200–240 V) [A]
12.5
15
20.5
24
32
46
59
111
172
Intermittent (1x200–240 V)
[A]
13.8
16.5
22.6
26.4
35.2
50.6
64.9
122.1
189.2
Maximum pre-fuses [A]
20
30
40
40
60
80
100
150
200
Additional specifications
Maximum cable cross-section
(mains, motor, brake) [mm
2
(AWG)]
0.2–4 (4–10)
10 (7)
35 (2)
50 (1/0)
95 (4/0)
Maximum cable cross-section
for mains with disconnect
switch [mm
2
(AWG)]
16 (6)
16 (6)
16 (6)
16 (6)
16 (6)
16 (6)
25 (3)
50 (1/0)
2 x 50 (2 x
1/0)
(1)(2)
Maximum cable cross-section
for mains without disconnect
switch [mm
2
(AWG)]
16 (6)
16 (6)
16 (6)
16 (6)
16 (6)
16 (6)
25 (3)
50 (1/0)
95 (4/0)
Cable insulation temperature
rating [°C (°F)]
75 (167) 75 (167) 75 (167) 75 (167) 75 (167) 75 (167) 75 (167) 75 (167) 75 (167)
Estimated power loss
(3)
at rat-
ed maximum load [W]
(4)
44
30
44
60
74
110
150
300
400
AJ300847815559en-000101 / 130R0337 | 71
Danfoss A/S © 2020.09
Specifications
VLT® AQUA Drive FC 202
Design Guide