10.4.3.15 Entry Holes, Enclosure Size C2, IP21
[5]
[3]
[2]
[6]
[4]
[1]
e3
0b
b6
62
.1
1
Table 61: Dimensions of Entry Holes for Enclosure Size C2, IP21
Hole number and recommended use
Dimensions
(1)
Nearest metric
UL [in]
[mm]
1) Mains
2
63.3
M63
2) Motor
2
63.3
M63
3) Brake/loadsharing
1 1/2
50.2
M50
4) Control cable
3/4
28.4
M25
5) Control cable
1/2
22.5
M20
6) Control cable
1/2
22.5
M20
1
Tolerance ±0.2 mm.
10.4.4 Tightening Torques for Cover
Table 62: Tightening Torque Values [Nm]
Enclosure size
IP20
IP21
IP55
IP66
A1
(1)
(2)
(2)
(2)
A2
(1)
(1)
(2)
(2)
A3
(1)
(1)
(2)
(2)
A4/A5
(2)
(2)
2
2
B1
(2)
(1)
2.2
2.2
B2
(1)
(2)
2.2
2.2
B3
(1)
(2)
(2)
(2)
B4
(1)
(2)
(2)
(2)
C1
(2)
(1)
2.2
2.2
C2
(2)
(1)
2.2
2.2
C3
2
(2)
(2)
(2)
C4
2
(2)
(2)
(2)
1
No screws to tighten.
2
Does not exist.
AJ300847815559en-000101 / 130R0337 | 121
Danfoss A/S © 2020.09
Electrical Installation
Considerations
VLT® AQUA Drive FC 202
Design Guide