6.11 Parameters: 40-** Mains / Filter
6.11.1 40-0* Mains Data
40-00 Mains Voltage
Range:
Function:
630 V
*
[[525-690 V]]
Set the mains voltage line to line.
40-01 Mains Frequency
Option:
Function:
[0]
*
50 Hz
Set the mains nominal frequency.
[1]
60 Hz
40-02 Mains Inductance
Range:
Function:
0.039 mH
*
[0.000 - 65.000
mH]
Set the Inductance of the mains.
This could be the transformer.
40-03 Mains Resistance
Range:
Function:
0.50 mOhm
*
[0.00 - 650.00
mOhm]
Set the value of the mains
resistance. This could be the
transformer.
6.11.2 40-1* LCL Filter
40-10 Mains Side Inductance (Lm)
Range:
Function:
0.029 mH
*
[0.000 - 65.000
mH]
Set the main side inductance
of the LCL filter.
40-11 Mains Side Resistance (Rm)
Range:
Function:
0.19 mOhm
*
[0.00 - 650.00
mOhm]
Set the main side resistance
of the LCL filter.
40-12 Converter Side Inductance (Lc)
Range:
Function:
0.100 mH
*
[0.000 - 65.000
mH]
Set the converter side
inductance of the LCL filter.
40-13 Converter Side Resistance (Rc)
Range:
Function:
0.48 mOhm
*
[0.00 - 650.00
mOhm]
Set the converter side
resistance of the LCL filter.
40-14 Filter Capacity (Cf)
Range:
Function:
400 uF
*
[0 - 65000 uF] Set the capacitance of the LCL filter.
The value is for the delta configuration.
How to Programme
Operating Instructions
64
Danfoss A/S © Rev. 05/2014 All rights reserved.
MG33X402