6.11.8 AF Settings 300-**
NOTE
Except for
300-10 Active Filter Nominal Voltage
, it is not
recommended to change the settings in this par. group for
the Low Harmonic Drive
Par. No. # Parameter description
Default value
4-set-up
FC 302
only
Change
during
operation
Conver-
sion
index
Type
300-0* General Settings
300-00
Harmonic Cancellation Mode
[0] Overall
All set-ups
TRUE
-
Uint8
300-01
Compensation Priority
[0] Harmonics
All set-ups
TRUE
-
Uint8
300-1* Network Settings
300-10
Active Filter Nominal Voltage
ExpressionLimit
2 set-ups
FALSE
0
Uint32
300-2* CT Settings
300-20
CT Primary Rating
ExpressionLimit
2 set-ups
FALSE
0
Uint32
300-22
CT Nominal Voltage
342 V
2 set-ups
FALSE
0
Uint32
300-24
CT Sequence
[0] L1, L2, L3
2 set-ups
FALSE
-
Uint8
300-25
CT Polarity
[0] Normal
2 set-ups
FALSE
-
Uint8
300-26
CT Placement
[1] Load Current
2 set-ups
FALSE
-
Uint8
300-29
Start Auto CT Detection
[0] Off
All set-ups
FALSE
-
Uint8
300-3* Compensation
300-30
Compensation Points
0.0 A
All set-ups
TRUE
-1
Uint32
300-35
Cosphi Reference
0.500 N/A
All set-ups
TRUE
-3
Uint16
300-4* Paralleling
300-40
Master Follower Selection
[2] Not Paralleled
2 set-ups
FALSE
-
Uint8
300-41
Follower ID
1 N/A
2 set-ups
FALSE
0
Uint32
300-42
Num. of Follower AFs
1 N/A
2 set-ups
FALSE
0
Uint32
300-5* Sleep Mode
300-50
Enable Sleep Mode
null
2 set-ups
TRUE
-
Uint8
300-51
Sleep Mode Trig Source
[0] Mains current
All set-ups
TRUE
-
Uint8
300-52
Sleep Mode Wake Up Trigger
ExpressionLimit
All set-ups
TRUE
0
Uint32
300-53
Sleep Mode Sleep Trigger
80 %
All set-ups
TRUE
0
Uint32
6.11.9 AF Readouts 301-**
Par.
No. #
Parameter description
Default value
4-set-up
FC 302
only
Change
during
operation
Conver-
sion
index
Type
301-0* Output Currents
301-00 Output Current [A]
0.00 A
All set-ups
TRUE
-2
Int32
301-01 Output Current [%]
0.0 %
All set-ups
TRUE
-1
Int32
301-1* Unit Performance
301-10 THD of Current [%]
0.0 %
All set-ups
TRUE
-1
Uint16
301-11 Estimated THD of Voltage [%]
0.0 %
All set-ups
Uint16
301-12 Power Factor
0.00 N/A
All set-ups
TRUE
-2
Uint16
301-13 Cosphi
0.00 N/A
All set-ups
TRUE
-2
Int16
301-14 Leftover Currents
0.0 A
All set-ups
TRUE
-1
Uint32
301-2* Mains Status
301-20 Mains Current [A]
0 A
All set-ups
TRUE
0
Int32
301-21 Mains Frequency
0 Hz
All set-ups
TRUE
0
Uint8
301-22 Fund. Mains Current [A]
0 A
All set-ups
TRUE
0
Int32
How to Programme
VLT Active Filter AAF 00x
82
MG.90.V2.02 - VLT® is a registered Danfoss trademark