8 General Specifications
8.1 Electrical Data
8.1.1 Power Rating
Grid conditions:
Supply voltage
380–480V
AC line voltage low / line drop-out:
During low AC line voltage or a line drop-out, the filter continues until the intermediate circuit voltage drops below the
minimum stop level, which corresponds typically to 15% below the filter lowest rated supply voltage. Full compensation cannot
be expected at AC line voltage lower than 10% below the filter lowest rated supply voltage. If AC line voltage exceeds the filter
highest rated voltage, the filter continues to work but harmonic mitigation performance is reduced. The filter will not cut out
until AC line voltages exceed 580V.
Supply frequency
50/60Hz ±5%
Max. imbalance temporary between line phases
where mitigation performance is kept high.
3.0% of rated supply voltage
The filter will mitigate at higher line imbalance but harmonic mitigation
performance is reduced
Max THDv pre-distortion
10% with kept mitigation performance
Reduced performance for higher pre-distortion levels
Harmonic Mitigation Performance:
THiD
Best performance <4%
Depending on filter vs. distortion ratio.
Individual harmonic mitigation ability:
% of filter current rating
5th
70%
7th
50%
11th
32%
13th
28%
17th
20%
19th
18%
23rd
16%
25th
14%
Total current of harmonics
90%
Reactive Current Compensation:
Cos phi
Controllable 1.0 to 0.5 lagging
Reactive current, % of filter current rating
100%
Cable lengths and cross-sections:
Max grid cable length
Unlimited (determined by voltage drop)
Maximum cross-section to control terminals, rigid wire
1.5mm
2
/16 AWG (2 x 0.75 mm
2
Maximum cross-section to control terminals, flexible cable
1mm
2
/18 AWG
Maximum cross-section to control terminals, cable with enclosed core
0.5mm
2
/20 AWG
Minimum cross-section to control terminals
0.25mm
2
CT terminals specification:
Necessary CT number
3 (one for each phase)
AAF's burden equals
2m
Ω
Secondary current rating
1A or 5A (hardware set-up)
Accuracy
Class 0.5 or better
General Specifications
VLT Active Filter AAF 00x
MG.90.V2.22 - VLT
®
is a registered Danfoss trademark
8-1
8
8
Содержание VLT AAF00x
Страница 1: ...MAKING MODERN LIVING POSSIBLE VLT Active Filter AAF00x Instruction Manual...
Страница 5: ...Contents VLT Active Filter AAF 00x MG 90 V2 22 VLT is a registered Danfoss trademark...
Страница 13: ...Introduction to VLT Active VLT Active Filter AAF 00x 3 4 MG 90 V2 22 VLT is a registered Danfoss trademark 3 3...
Страница 59: ...How to Operate the Active F VLT Active Filter AAF 00x 5 8 MG 90 V2 22 VLT is a registered Danfoss trademark 5 5...
Страница 95: ...How to Program VLT Active Filter AAF 00x 6 36 MG 90 V2 22 VLT is a registered Danfoss trademark 6 6...
Страница 103: ...RS 485 Installation and set VLT Active Filter AAF 00x 7 8 MG 90 V2 22 VLT is a registered Danfoss trademark 7 7...
Страница 117: ...www danfoss com drives MG90V222 130R0506 MG90V222 Rev 2011 06 17...