VLT
®
8000 AQUA
See also parameter 216
Frequency bypass, bandwidth
.
221 Warning: Low current, I
LOW
(WARN. LOW CURR.)
Value:
0.0 - par. 222
Warning: High current I
HIGH
,
✭
0.0A
Function:
When the motor current is below the limit, I
LOW
,
programmed in this parameter, the display shows a
flashing CURRENT LOW, provided
Warning
[1] has
been selected in parameter 409
Function in case of no
load
. The frequency converter will trip if parameter 409
Function in case of no load
has been selected as
Trip
[0].
The warning functions in parameters 221-228 are
not active during ramp-up after a start command,
ramp-down after a stop command or while
stopped. The warning functions are activated when
the output frequency has reached the resulting
reference. The signal outputs can be programmed
to generate a warning signal via terminal 42 or
45 and via the relay outputs.
Description of choice:
The lower signal limit I
LOW
must be programmed within
the normal working range of the frequency converter.
222 Warning: High current, I
HIGH
(WARN. HIGH CURR.)
Value:
Parameter 221 - I
VLT,MAX
✭
I
VLT,MAX
Function:
If the motor current is above the limit, I
HIGH
,
programmed in this parameter, the display shows
a flashing CURRENT HIGH.
The warning functions in parameters 221-228 are
not active during ramp-up after a start command,
ramp-down after a stop command or while stopped.
The warning functions are activated when the output
frequency has reached the resulting reference.
The signal outputs can be programmed to
generate a warning signal via terminal 42 or
45 and via the relay outputs.
Description of choice:
The upper signal limit of the motor frequency, f
HIGH
,
must be programmed within the normal working
range of the frequency converter. See drawing at
parameter 221
Warning: Low current, I
LOW
.
223 Warning: Low frequency, f
LOW
(WARN. LOW FREQ.)
Value:
0.0 - parameter 224
✭
0.0 Hz
Function:
If the output frequency is below the limit, f
LOW
,
programmed in this parameter, the display will
show a flashing FREQUENCY LOW.
The warning functions in parameters 221-228 are
not active during ramp-up after a start command,
ramp-down after a stop command or while stopped.
The warning functions are activated when the output
frequency has reached the selected reference.
The signal outputs can be programmed to
generate a warning signal via terminal 42 or
45 and via the relay outputs.
Description of choice:
The lower signal limit of the motor frequency, f
LOW
,
must be programmed within the normal working
range of the frequency converter. See drawing at
parameter 221
Warning: Low current, I
LOW
.
224 Warning: High frequency, f
HIGH
(WARN. HIGH FREQ.)
Value:
Par. 200
Output frequency range
= 0-120 Hz [0].
parameter 223 - 120 Hz
✭
120.0 Hz
Function:
If the output frequency is above the limit, f
HIGH
,
programmed in this parameter, the display will
show a flashing FREQUENCY HIGH.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.83.A2.02 - VLT is a registered Danfoss trademark
114
Содержание VLT 8000 AQUA series
Страница 29: ...VLT 8000 AQUA Introduction TYPE CODE Table Ordering form MG 83 A2 02 VLT is a registered Danfoss trademark 29 ...
Страница 52: ...VLT 8000 AQUA Mechanical dimensions MG 83 A2 02 VLT is a registered Danfoss trademark 52 ...
Страница 60: ...VLT 8000 AQUA All enclosure types VLT 8152 8652 380 480 V MG 83 A2 02 VLT is a registered Danfoss trademark 60 ...
Страница 63: ...VLT 8000 AQUA Installation MG 83 A2 02 VLT is a registered Danfoss trademark 63 ...