VLT
®
8000 AQUA
Programming
206 Ramp-up time
(RAMP UP TIME)
Value:
1 - 3600 sec.
✭
Depends on the unit
Function:
The ramp-up time is the acceleration time from 0
Hz to the rated motor frequency f
M,N
(parameter
104
Motor frequency, f
M,N
). It is assumed that the
output current does not reach the current limit (set
in parameter 215
Current limit I
LIM
).
Description of choice:
Program the desired ramp-up time.
207 Ramp-down time
(RAMP DOWN TIME)
Value:
1 - 3600 sec.
✭
Depends on the unit
Function:
The ramp-down time is the deceleration time
from the rated motor frequency f
M,N
(parameter
104
Motor frequency, f
M,N
) to 0 Hz, provided
there is no overvoltage in the inverter because of
the motor acting as a generator.
Description of choice:
Program the desired ramp-down time.
208 Automatic ramp-down
(AUTO RAMPING)
Value:
Disable (DISABLE)
[0]
✭
Enable (ENABLE)
[1]
Function:
This function ensures that the frequency converter
does not trip during deceleration if the ramp-down
time set is too short. If, during deceleration, the
frequency converter registers that the intermediate
circuit voltage is higher than the max. value (see
list
of warnings and alarms
), the frequency converter
automatically extends the ramp-down time.
NB!:
If the function is chosen as
Enable
[1], the ramp
time may be considerably extended in relation to
the time set in parameter 207
Ramp-down time
.
Description of choice:
Program this function as
Enable
[1] if the frequency
converter periodically trips during ramp-down. If a
quick ramp-down time has been programmed that
may lead to a trip under special conditions, the function
can be set to
Enable
[1] to avoid trips.
209 Jog frequency
(JOG FREQUENCY)
Value:
Par. 201
Output frequency Low limit
- par. 202
Output frequency high limit
✭
10.0 HZ
Function:
The jog frequency f
JOG
is the fixed output frequency
at which the frequency converter is running when
the jog function is activated.
Jog can be activated via the digital inputs.
Description of choice:
Set the desired frequency.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.83.A2.02 - VLT is a registered Danfoss trademark
111
Содержание VLT 8000 AQUA series
Страница 29: ...VLT 8000 AQUA Introduction TYPE CODE Table Ordering form MG 83 A2 02 VLT is a registered Danfoss trademark 29 ...
Страница 52: ...VLT 8000 AQUA Mechanical dimensions MG 83 A2 02 VLT is a registered Danfoss trademark 52 ...
Страница 60: ...VLT 8000 AQUA All enclosure types VLT 8152 8652 380 480 V MG 83 A2 02 VLT is a registered Danfoss trademark 60 ...
Страница 63: ...VLT 8000 AQUA Installation MG 83 A2 02 VLT is a registered Danfoss trademark 63 ...