VLT® 7000 Booster
Cascade Controller
Settings
■
Cascade Controller Settings
■
Operation modes
The following table gives an overview of the 14 available
modes in the VLT 7000 Booster. Below the table a
description of the different terms is given.
Mode
No
Control type
AUX pump available?
Staging and destaging
order
Default value for digital input
on terminal 18 (DI 18)
No. of pumps incl.
AUX pump
1
No
FILO
DI 18: (NO OPERATION)
2 - 7
2
No
FILO
DI 18: (START)
2 - 7
3
No
LRHIMRHO
DI 18: (NO OPERATION)
2 - 7
4
Fixed lead pump
No
LRHIMRHO
DI 18: (START)
2 - 7
5
control
Yes - R78
FILO
DI 18: (NO OPERATION)
2 - 7
6
Yes - R78
FILO
DI 18: (START)
2 - 7
7
Yes - R78
LRHIMRHO
DI 18: (NO OPERATION)
2 - 7
8
Yes - R78
LRHIMRHO
DI 18: (START)
2 - 7
9
No
LRHIMRHO
DI 18: (NO OPERATION)
2 - 4
10
No
LRHIMRHO
DI 18: (START)
2 - 4
11
Alternating lead
Yes - R78
LRHIMRHO
DI 18: (NO OPERATION)
2 - 4
12
pump control
Yes - R78
LRHIMRHO
DI 18: (START)
2 - 4
13
Yes - CCR
LRHIMRHO
DI 18: (NO OPERATION)
2 - 5
14
Yes - CCR
LRHIMRHO
DI 18: (START)
2 - 5
■
Mode no
The mode no is the mode number which is
to be selected in the VLT menu, please refer
to parameter settings.
MG.70.A1.02 - VLT is a registered Danfoss trademark
93