VLT® 7000 Booster
Programming
207 Ramp-down time
(RAMP DOWN TIME)
Value:
1 - 60 sec.
✭
Depends on the unit
Function:
The ramp-down time is the deceleration time
from the rated motor frequency f
M,N
(parameter
104
Motor frequency, f
M,N
) to 0 Hz, provided
there is no overvoltage in the inverter because of
the motor acting as a generator.
Description of choice:
Program the desired ramp-down time.
208 Automatic ramp-down
(AUTO RAMPING)
Value:
Disable (DISABLE)
[0]
✭
Enable (ENABLE)
[1]
Function:
This function ensures that the frequency converter
does not trip during deceleration if the ramp-down
time set is too short. If, during deceleration, the
frequency converter registers that the intermediate
circuit voltage is higher than the max. value (see
list
of warnings and alarms
), the frequency converter
automatically extends the ramp-down time.
NB!:
If the function is chosen as
Enable
[1], the ramp
time may be considerably extended in relation to
the time set in parameter 207
Ramp-down time
.
Description of choice:
Program this function as
Enable
[1] if the frequency
converter periodically trips during ramp-down. If a
quick ramp-down time has been programmed that
may lead to a trip under special conditions, the function
can be set to
Enable
[1] to avoid trips.
209 Jog frequency
(JOG FREQUENCY)
Value:
Par. 201
Output frequency Low limit
- par. 202
Output frequency high limit
✭
10.0 HZ
Function:
The jog frequency f
JOG
is the fixed output frequency
at which the frequency converter is running when
the jog function is activated.
Jog can be activated via the digital inputs.
Description of choice:
Set the desired frequency.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.70.A1.02 - VLT is a registered Danfoss trademark
63