VLT® 7000 Booster
Programming
■
Load and Motor 100-117
This parameter group allows
the con-figuration of regulation
parameters and the choice of
torque characteristics to which
the frequency converter is to be
adapted.
The motor nameplate data must
be
set and automatic motor adaptation can be carried
out. In addition, DC brake parameters can be set
and the motor thermal protection can be activated.
■
Configuration
The selection of configuration and torque characteristics
influences the parameters that can be seen in the
display. If
Open loop
[0] is selected, all parameters
relating to PID regulation will be hidden.
Consequently, the user is only able to see
the parameters that are of significance for
a given application.
100 Configuration
(CONFIG. MODE)
Value:
Closed loop (CLOSED LOOP)
[1]
Function:
Only
closed loop
is available.
Open loop
is only possible
in local reference or remote reference. See par. 203.
Description of choice:
The internal process regulator is activated to enable
accurate regulation in relation to a given process signal.
The reference (setpoint) and the process signal
(feedback) can be set to a process unit as
programmed in parameter 415
Process units
. See
Feedback handling
.
101 Torque characteristics
(VT CHARACT)
Value:
✭
Automatic Energy Optimisation
(AEO FUNCTION)
[0]
Parallel motors (MULTIPLE MOTORS)
[1]
Function:
This parameter allows a choice of whether the frequency
converter has one or several motors connected to it.
Description of choice:
If Automatic Energy Optimisation [0] has been
selected, only one motor may be connected to the
frequency converter. The AEO function ensures
that the motor obtains its maximum efficiency and
minimises motor interference.
Select Parallel motors
[1] if more than one motor is connected to the output
in parallel. See the description under parameter
108
Start voltage of parallel motors
regarding the
setting of parallel motor start voltages.
102 Motor power, P
M,N
(MOTOR POWER)
Value:
0.25 kW (0.25 KW)
[25]
0.37 kW (0.37 KW)
[37]
0.55 kW (0.55 KW)
[55]
0.75 kW (0.75 KW)
[75]
1.1 kW (1.10 KW)
[110]
1.5 kW (1.50 KW)
[150]
2.2 kW (2.20 KW)
[220]
3 kW (3.00 KW)
[300]
4 kW (4.00 KW)
[400]
5,5 kW (5.50 KW)
[550]
7,5 kW (7.50 KW)
[750]
11 kW (11.00 KW)
[1100]
15 kW (15.00 KW)
[1500]
18.5 kW (18.50 KW)
[1850]
22 kW (22.00 KW)
[2200]
30 kW] (30.00 KW)
[3000]
37 kW (37.00 KW)
[3700]
45 kW (45.00 KW)
[4500]
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.70.A1.02 - VLT is a registered Danfoss trademark