VLT® 7000 Booster
■
Technical data, mains supply 3x380-460V
According to international requirements
VLT type
7052
7062
7072
Output current
I
VLT,N
[A] (380-440 V)
73.0
90.0
106
I
VLT, MAX
(60 s) [A] (380-440 V)
80.3
99.0
117
I
VLT,N
[A] (441-460 V)
65.0
77.0
106
I
VLT, MAX
(60 s) [A] (441-460 V)
71.5
84.7
117
Output power
S
VLT,N
[kVA] (400 V)
52.5
64.7
73.4
S
VLT,N
[kVA] (460 V)
51.8
61.3
84.5
Typical shaft output
P
VLT,N
[kW]
37
45
55
Typical shaft output
P
VLT,N
[HP]
50
60
75
Max. cable cross-section to
motor and DC-bus, IP 20
[mm
2
]/[AWG]
2) 4) 5)
35/2
50/0
50/0
Min. cable cross-section to
motor and DC-bus
[mm
2
]/[AWG]
2) 4)
10/8
16/6
16/6
Max. input current
I
L,N
[A] (380 V)
72.0
89.0
104
(RMS)
I
L,N
[A] (460 V)
64.0
77.0
104
Max. cable cross-section
power, IP 20
[mm
2
]/[AWG]
2) 4) 5)
35/2
50/0
50/0
Max. pre-fuses
[-]/UL
1)
[A]
100/100
125/125
150/150
Mains contactor
[Danfoss type]
CI 37
CI 61
CI 85
Efficiency at rated frequency
0.96
0.96
0.96
Weight IP 20
[kg]
41
42
43
Power loss at max. load.
[W]
1275
1571
1851
Enclosure
IP 20
1. For type of fuse, see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Max. cable cross
section is the maximum possible cable cross section that can be fitted on the terminals.
Always comply with national and local regulations on min. cable cross-section.
5. Aluminium cables with cross-section above 35 mm
2
must be connected by use of an Al-Cu connector.
■
Fuses
Non UL compliance
If UL/cUL is not to be complied with, we recommend the above mentioned fuses or:
VLT 7002-7072
380-460 V
type gG
Not following the recommendation may result
in unnecessary damage of the drive in case of
malfunction. Fuses must be designed for protection in
a circuit capable of supplying a maximum of 100000
A
rms
(symmetrical), 500 V/600 V maximum.
MG.70.A1.02 - VLT is a registered Danfoss trademark
20