VLT® 7000 Booster
Staging and destaging
og fixed speed pumps
■
Staging and destaging of pumps in mode 9-14
Parameter 710 is only to be set, when operating
mode 9-14 is selected.
The adjustable speed pump typically runs at maximum
speed when staging on an additional fixed speed
pump to match the system demand. When staging on
another pump, the VLT will coast and after a time delay
set i par. 710, the pump will be switched to mains. The
VLT will finally bring the next pump in line up in speed.
■
Quick menu 27 Par. 710 Delay before
running on mains
Par. 710 Delay before running on mains
(DELAY BEF. MAINS)
Value:
100 ms - 2000 ms
✭
500 ms
Function:
Time delay to ensure sufficient de-magnetisation of
the motor before switching it to mains.
Description of choice:
Set the delay before running on mains.
NB!:
The destaging of a pump in any of the modes
9-14 is done in the same way as for modes 1-8,
please refer to quick menu 26 parameter 709.