VLT
®
6000 HVAC Series
■
Technical data, mains supply 3 x 380-460V
According to international requirements
VLT type
6002
6003
6004
6005
6006
6008
6011
Output current
I
VLT,N
[A] (380-440
V)
3.0
4.1
5.6
7.2
10.0
13.0
16.0
I
VLT, MAX
(60 s) [A]
(380-440 V)
3.3
4.5
6.2
7.9
11.0
14.3
17.6
I
VLT, N
[A] (441-460
V)
3.0
3.4
4.8
6.3
8.2
11.0
14.0
I
VLT, MAX
(60 s) [A]
(441-460 V)
3.3
3.7
5.3
6.9
9.0
12.1
15.4
Output power
S
VLT,N
[kVA] (400 V)
2.2
2.9
4.0
5.2
7.2
9.3
11.5
S
VLT,N
[kVA] (460 V)
2.4
2.7
3.8
5.0
6.5
8.8
11.2
Typical shaft
output
P
VLT,N
[kW]
1.1
1.5
2.2
3.0
4.0
5.5
7.5
Typical shaft
output
P
VLT,N
[HP]
1.5
2
3
-
5
7.5
10
Max. cable
cross-section to
motor
[mm
2
]/[AWG]
2) 4)
4/10
4/10
4/10
4/10
4/10
4/10
4/10
Max.
input
current
I
L,N
[A] (380 V)
2.8
3.8
5.3
7.0
9.1
12.2
15.0
(RMS)
I
L,N
[A] (460 V)
2.5
3.4
4.8
6.0
8.3
10.6
14.0
Max. cable
cross-section
power
[mm
2
]/[AWG]
2) 4)
4/10
4/10
4/10
4/10
4/10
4/10
4/10
Max. pre-fuses
[-]/UL
1)
[A]
16/6
16/10
16/10
16/15
25/20
25/25
35/30
Efficiency
3)
0.96
0.96
0.96
0.96
0.96
0.96
0.96
Weight IP 20
[kg]
8
8
8.5
8.5
10.5
10.5
10.5
Weight IP 54
[kg]
11.5
11.5
12
12
14
14
14
Power loss at
max. load. [W]
Total
67
92
110
139
198
250
295
Enclosure
VLT type
IP 20/IP 54
1. For type of fuse, see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross section is the maximum possible cable cross section that can be fitted on the terminals.
Always comply with national and local regulations on min. cable cross-section.
MG.61.A5.02 - VLT is a registered Danfoss trademark