
VLT
®
6000 HVAC Series
■
Technical data, mains supply 3 x 200-240V
According to international requirements
VLT type
6002
6003
6004
6005
6006
6008
6011
Output current
4)
I
VLT,N
[A]
6.6
7.5
10.6
12.5
16.7
24.2
30.8
I
VLT, MAX
(60 s) [A]
7.3
8.3
11.7
13.8
18.4
26.6
33.9
Output power (240 V)
S
VLT,N
[kVA]
2.7
3.1
4.4
5.2
6.9
10.1
12.8
Typical shaft output
P
VLT,N
[kW]
1.1
1.5
2.2
3.0
4.0
5.5
7.5
Typical shaft output
P
VLT,N
[HP]
1.5
2
3
4
5
7.5
10
Max.
cable
cross-section to
motor
and DC-bus
[mm
2
]/[AWG]
4/10
4/10
4/10
4/10
10/8
16/6
16/6
Max. input current
(200 V) (RMS)I
L,N
[A]
6.0
7.0
10.0
12.0
16.0
23.0
30.0
Max. cable
cross-section power
[mm
2
]/[AWG]
2 )
4/10
4/10
4/10
4/10
4/10
16/6
16/6
Max. pre-fuses
[-]/UL
1)
[A]
16/10
16/15
25/20
25/25
35/30
50
60
Efficiency
3)
0.95
0.95
0.95
0.95
0.95
0.95
0.95
Weight IP 20
[kg]
7
7
9
9
23
23
23
Weight IP 54
[kg]
11.5
11.5
13.5
13.5
35
35
38
Power loss at
max. load. [W]
Total
76
95
126
172
194
426
545
Enclosure
VLT type
IP 20 / IP 54
1. For type of fuse, see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Current ratings fulfill UL requirements for 208-240 V.
MG.61.A5.02 - VLT is a registered Danfoss trademark
26