Mechanical installation
Please pay attention to the requirements
that apply to integration and field mounting
kit, see the below list. The information given
in the list must be observed to avoid serious damage
or injury, especially when installing large units.
The frequency converter
must
be installed vertically.
The frequency converter is cooled by means of air
circulation. For the unit to be able to release its cooling
air, the
minimum
distance over and below the unit
must be as shown in the illustration below.
To protect the unit from overheating, it must be
ensured that the ambient temperature
does not rise
above the max. temperature stated for the frequency
converter
and that the 24-hour average temperature
is
not exceeded
. The max. temperature and 24-hour
average can be seen from the
General Technical Data
.
If the ambient temperature is in the range of 45°C -55°
C, derating of the frequency converter will become
relevant, see
Derating for ambient temperature
.
The service life of the frequency converter will
be reduced if derating for ambient temperature
is not taken into account.
■
Installation of VLT 6002-6352
All frequency converters must be installed in a
way that ensures proper cooling.
Cooling
All Bookstyle and Compact units require a minimum
space above and below the enclosure.
Side by side/flange by flange
All frequency converters can be mounted side
by side/flange by flange.