VLT
®
5000 FLUX
323 Relay 01, output
(RELAY 1-3 FUNCT.)
Value:
See table in section
Digital Outputs.
Function:
This output activates a two-way relay.
Relay information 01 can be used for bringing status and
warnings. The relay is activated when the conditions
for the relevant data values have been fulfilled.
Activation/deactivation can be delayed in
parameter 324/325.
Description of choice:
See description in section
Digital and relay outputs.
Connections - see the drawing below.
Max. terminal load (AC) on 1-3,
1-2, power card
240 V AC, 2 A, 60 VA
Max. terminal load on 1-3, 1-2,
power card
50 V DC, 2 A
Min. terminal load on 1-3, 1-2,
power card
24 V DC 10 mA, 24 V
AC 100 mA
324 Relay 01, ON delay
(RELAY 1-3 ON DL)
Value:
0.00 - 600.00.
✭
0.00 sec.
Function:
This parameter allows a delay of the cut-in time
of relay 01 (terminals 01-02).
Description of choice:
Enter the desired value (can be set at intervals
of 0.02 sec.).
325 Relay 01, OFF delay
(RELAY 1-3 OFF DL)
Value:
0.00 - 600.00
✭
0.00 sec.
Function:
This parameter makes it possible to delay the cut-out
time of relay 01 (terminals 01-03).
Description of choice:
Enter the desired value (can be set at intervals
of 0.02 sec.).
326 Relay 04, output
(RELAY 4-5 FUNCT.)
Value:
See description of parameter 319.
Function:
This output activates a make relay.
Relay switch 04 can be used for bringing status and
warnings. The relay is activated when the conditions
for the relevant data values have been fulfilled.
Description of choice:
See description in section
Digital and relay outputs
.
Connections - see the below drawing.
Max. terminal load (AC) on 4-5,
control card
50 V AC, 1 A, 60 VA
Max. terminal load (DC) on 4-5,
control card
75 V DC, 0.1 A, 30 W
Max. terminal load (DC) on
4-5, control card for UL/cUL
applications
30 V AC, 1 A / 42.5 V
DC, 1A
327 Pulse reference, max. frequency
(PULSE REF MAX)
Value:
100 - 65000 Hz at terminal 29
✭
5000 Hz
Function:
In this parameter, the signal value is set that corresponds
to the maximum reference value set in parameter 205.
Description of choice:
Set the desired pulse reference.
329 Encoder feedback pulse/rev.
(ENCODER PULSES)
Value:
512 pulses /rev. (512)
[512]
✭
1024 pulses /rev. (1024)
[1024]
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A6.02 - VLT is a registered Danfoss trademark
98
Содержание VLT 5000 FLUX
Страница 12: ...VLT 5000 FLUX Key Diagram for VLT 5032 5052 200 240 V MG 55 A6 02 VLT is a registered Danfoss trademark 12 ...
Страница 15: ...VLT 5000 FLUX Technical data Mechanical dimensions cont MG 55 A6 02 VLT is a registered Danfoss trademark 15 ...
Страница 39: ...VLT 5000 FLUX All about FCD 300 MG 55 A6 02 VLT is a registered Danfoss trademark 39 ...