VLT
®
5000 FLUX
Programming
■
References and limits
■
Introduction
The purpose of the parameter group 2xx is selecting and adjusting references, ramping times and setting
limits for warnings.
Actual reference
Resulting reference for speed/torque
External reference
Reference on Terminals 53, 54 or 60, and puls and bus references
Preset reference
Reference value from the internal four presets.
PNU
Parameter
Factory setting
Range
Changes
4-Setup
Conversion
Data
#
description
during operation
index
type
200
Output speed range/direction
Only clockwise, 0-4500
rpm
No
Yes
0
5
202
Output speed high limit
3000 rpm
n
MIN
- par. 200
No
Yes
-1
6
203
Reference Range
Min - max
Yes
Yes
0
5
204
Minimum reference
0.000
-100,000.000-Ref
MAX
Yes
Yes
-3
4
205
Maximum reference
1500.000
Ref
MIN
-100,000.000
Yes
Yes
-3
4
206
Ramp type
Linear
Yes
Yes
0
5
207
Ramp-up time 1
Depends on unit
0.01 - 3600
Yes
Yes
-2
7
208
Ramp-down time 1
Depends on unit
0.01 - 3600
Yes
Yes
-2
7
209
Ramp-up time 2
Depends on unit
0.01 - 3600
Yes
Yes
-2
7
210
Ramp-down time 2
Depends on unit
0.01 - 3600
Yes
Yes
-2
7
211
Jog ramp time
Depends on unit
0.01 - 3600
Yes
Yes
-2
7
212
Quick stop ramp-down time
Depends on unit
0.01 - 3600
Yes
Yes
-2
7
213
Jog speed
200 rpm
0.0 - par. 202
Yes
Yes
-1
6
214
Reference function
Sum
Yes
Yes
0
5
215
Preset reference 1
0.00 %
- 100.00 - 100.00 %
Yes
Yes
-2
3
216
Preset reference 2
0.00 %
- 100.00 - 100.00 %
Yes
Yes
-2
3
217
Preset reference 3
0.00 %
- 100.00 - 100.00 %
Yes
Yes
-2
3
218
Preset reference 4
0.00 %
- 100.00 - 100.00 %
Yes
Yes
-2
3
219
Catch up/slow down value
0.00 %
0.00 - 100 %
Yes
Yes
-2
6
221
Torque limit for motor mode
160 %
0.0 % - xxx %
Yes
Yes
-1
6
222
Torque limit for generating
operation
160 %
0.0 % - xxx %
Yes
Yes
-1
6
223
Warning: Low current
0.0 A
0.0 - par. 224
Yes
Yes
-1
6
224
Warning: High current
I
VLT,MAX
Par. 223 - I
VLT,MAX
Yes
Yes
-1
6
225
Warning: Low speed
0 rpm
0 - par. 226
Yes
Yes
-1
6
226
Warning: High speed
100.000 rpm
Par. 225 - par. 202
Yes
Yes
-1
6
234
Motor phase monitor
Enable
Yes
Yes
0
5
235
Phase loss monitor
Enable
No
No
0
5
236
Low Speed Current
100%
0 – Motor size depended Yes
Yes
0
6
237
Model Shift Speed
20% of n
nom
10 Hz
Yes
No
0
6
240
Acceleration Jerk 1
33%
0-100%
No
No
0
U16
241
Acceleration Jerk 2
33%
0-100%
No
No
0
U16
242
Deceleration Jerk 1
33%
0-100%
No
No
0
U16
243
Deceleration Jerk 2
33%
0-100%
No
No
0
U16
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A6.02 - VLT is a registered Danfoss trademark
79