152 Stator Leakage Reactance
(STATOR LEAKAGE)
Value:
Ohm
✭
Depends on unit
Function:
Set the stator leakage reactance of the motor.
Description of choice:
X
1
can be set as follows:
1. Automatic Motor Adaptation, where the
frequency converter measures on the motor
to determine the value.
2. The motor supplier states the value.
3. The factory setting of X
1
, selected by the
frequency converter itself on the basis of the
motor nameplate data, is used.
153 Rotor Leakage Reactance
(ROTOR LEAKAGE)
Value:
Ohm
✭
Depends on unit
Function:
Set the rotor leakage reactance of the motor.
Description of choice:
X
2
can be set as follows:
1. Automatic Motor Adaptation, where the
frequency converter measures on the motor
to determine the value.
2. The motor supplier states the value.
3. The factory setting of X
2
, selected by the
frequency converter itself on the basis of the
motor nameplate data, is used.
154 Main Reactance
(MAIN REACTANCE)
Value:
Ohm
✭
Depends on unit
Function:
Set the main reactance of the motor.
Description of choice:
X
h
can be set as follows:
1. Automatic Motor Adaptation, where the
frequency converter measures on the motor
to determine the value.
2. The motor supplier states the value.
3. The factory setting of X
h
, selected by the
frequency converter itself on the basis of the
motor nameplate data, is used.
156 Pole Number (POLE NUMBER)
Value:
Depends on motor type
Value 2 - 100 poles
✭
4-pole motor
Function:
Set the pole number of the motor
Description of choice:
Poles
~ n
n
@ 50 Hz
~ n
n
@ 60Hz
2
2700 - 2880
3250 - 3460
4
1350 - 1450
1625 - 1730
6
700 - 960
840 - 1153
The above table shows the normal speed range
for various motor types. Motors designed for other
frequencies must be defined separately.
158 Iron loss Resistance
(IRONLOSS RES.)
Value:
1 -10.000
✭
10.000
Function:
Set the equivalents of the R
Fe
to compensate
for iron losses in the motor.
Description of choice:
The function is switched off when the value
10.000 is chosen.
The Iron loss resistance most be less than:
R
Fe
< P
0
/ I
0
2
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A6.02 - VLT is a registered Danfoss trademark
76
Содержание VLT 5000 FLUX
Страница 12: ...VLT 5000 FLUX Key Diagram for VLT 5032 5052 200 240 V MG 55 A6 02 VLT is a registered Danfoss trademark 12 ...
Страница 15: ...VLT 5000 FLUX Technical data Mechanical dimensions cont MG 55 A6 02 VLT is a registered Danfoss trademark 15 ...
Страница 39: ...VLT 5000 FLUX All about FCD 300 MG 55 A6 02 VLT is a registered Danfoss trademark 39 ...