VLT
®
5000 FLUX
Miscellaneous
(BRAKE IGBT FAULT) [2]
The brake IGBT has short-circuited. This fault means
that the unit is not able to stop the brake and that,
consequently, the resistor is constant being energized.
WARNING/ALARM: 44
Encoder loss (ENCODER FAULT)
The encoder signal is interrupted from terminal
32 or 33. Check the connections.
LEDs on encoder board:
When all LEDs are ON the connection to encoder
and encoder condition are OK.
LED 403 OFF: 5 V supply missing
LED 400 OFF: Channel A or inv. A missing
or shortcircuited
LED 401 OFF: Channel B or inv. B missing
or shortcircuited
LED 402 OFF: Channel Z or inv. Z missing
or shortcircuited.
ALARM 48:
Tracking fault
The following events can generate Alarm 48:
•
Parameter 361 set too low: Extend the range
•
Wrong encoder direction: Motor goes one way,
the encoder goes the other way
•
Running in torque limit: Insufficient torque to follow
the ramp, hitting an obstruction, etc.
•
Bad PID settings: Oscillations can produce
large errors. Readjust the PID control
(Parameters 417 and 418)
■
Warning word 1, Extended status word
and Alarm word
Warning word 1, extended status word and alarm
word are shown on the display in Hex format. If
there are more than one warning or alarm, a sum
of all warnings or alarms will be shown.
Warning word 1, extended status word and alarm
word can also be displayed using the serial bus
in parameter 540, 541 and 538.
Bit (Hex)
Warning word 1 (parameter 540)
000001
Fault during brake test
000002
EE-prom power card fault
000004
EE-prom control card
000008
HPFP bus timeout
000010
Standard bus timeout
000020
Overcurrent
000040
Torque limit
000080
Motor thermistor
000100
Motor overload
000200
Inverter overload
000400
Undervoltage
000800
Overvoltage
001000
Voltage warning low
002000
Voltage warning high
004000
Phase fault
008000
No motor
010000
Live zero fault
(4-20 mA current signal low)
020000
10 Volts low
040000
Brake resistor power 100%
080000
Brake resistor fault
100000
Brake transistor fault
200000
Out of frequency range
400000
Fieldbus communication fault
800000
Encoder loss
1000000
Mains failure
2000000
Motor too small
4000000
Motor too big
8000000
Check P. 103 and P. 105
10000000
Check P. 104 and P. 106
20000000
Application high
40000000
Application low
80000000
Warning word 2
MG.55.A6.02 - VLT is a registered Danfoss trademark
129
Содержание VLT 5000 FLUX
Страница 12: ...VLT 5000 FLUX Key Diagram for VLT 5032 5052 200 240 V MG 55 A6 02 VLT is a registered Danfoss trademark 12 ...
Страница 15: ...VLT 5000 FLUX Technical data Mechanical dimensions cont MG 55 A6 02 VLT is a registered Danfoss trademark 15 ...
Страница 39: ...VLT 5000 FLUX All about FCD 300 MG 55 A6 02 VLT is a registered Danfoss trademark 39 ...