VLT® 5000 Crane
All About VLT 5000
Crane
■
Warnings and Alarms, 29-49
Warn-
ings/Alarm
numbers
Display
Description
How to Handle
29 (w)
Heat Sink Over Temp
For IP20/IP 00, the cut-out temperature if the heat
sink is 90°C. The tolerance is +/- 5°C.
Decrease ambient temperature and
check fans
30 (a)
Missing Mot.Phase U
Motor phase U between frequency converter and
motor is missing
Turn off the frequency converter and
check motor phase U
31 (a)
Missing Mot.Phase V
Motor phase V between frequency converter and
motor is missing
Turn off the frequency converter and
check motor phase V
32 (a)
Missing Mot.Phase
W
Motor phase W between frequency converter and
motor is missing
Turn off the frequency converter and
check motor phase W
35 (w)
Motor Not Ready
The drive was unable to finish the starting sequence
(pre-magnetisation and start torque) within 5 sec.
Check the motor connection
37 (a)
Inverter Fault
IGBT or the power card is defective
Contact your Danfoss supplier
43 (a)
Brake Fault
A fault has arisen on the brake chopper. The text
shown in the display indicates a fault message.
The figure in square brackets is the fault code that
can be seen in the fault log, parameter 615
[0] The brake resistor check carried out
during power-up indicates that the brake
has been disconnected. Check whether
the brake has been connected correctly
and that it has not been dispconnected
[1] The brake output has short-circuited.
Replace the brake resistor
[2] The brake IGBT has short-circuited.
This fault means that the unit is not able
to stop the brake and that, consequently,
the resistor is constantly being energized
44 (a)
Encoder fault
The encoder signal is interrupted from terminal 73,
74, 75, 76, 77 or 78
Check the connections
45 (a)
Load fault
An overload has occurred on one or both of the
load contacts and the speed is too high to hold the
load. The overload causes a trip
Start up again with reduced speed
46 (a)
Watchdog fault
An internal error has occurred
Contact your Danfoss supplier
47 (a)
Flash fault
An internal error has occurred
Contact your Danfoss supplier
48 (a)
Tracking fault
Load is dropping faster than expected
Check mechanical brake
49 (w)
Brake release fault
Fault when releasing the brake (open).
50 (w)
Brake activate fault
Fault when activating the brake (close)
Remove the start signal
MG.50.N4.02 - VLT is a registered Danfoss trademark