4 Programming
4.1 Operation & Display
001
Language
Value:
English (english)
[0]
German (deutsch)
[1]
French (francais)
[2]
Danish (dansk)
[3]
Spanish (espanol)
[4]
Italian (italiano)
[5]
Function:
This parameter is used to select the language to be shown
in the display whenever the LCP control unit is connected.
Description of choice:
There is a choice of the languages shown. The factory
setting may vary.
002
Local/Remote Operation
Value:
Remote operation (REMOTE)
[0]
Local operation (LOCAL)
[1]
Function:
2 different operation modes of the frequency converter are
available.
[0] Remote operation
or
[1] Local operation
. See
also
parameter 013 Local control
if
[1] Local operation
is
selected.
Description of choice:
If
[0] Remote operation
is selected, the frequency converter
is controlled via:
•
The control terminals or via serial communication.
•
The [START] key. This cannot, however, override
stop commands transmitted via the digital inputs
or via serial communication.
•
The [STOP/RESET] and [JOG] keys, on the
condition that these are active.
If
[1] Local operation
is selected, the frequency converter is
controlled via:
•
The [START] key. This cannot, however, override
stop commands via the digital inputs (see
parameter 013 Local control
).
•
The [STOP/RESET] and [JOG] keys, on the
condition that these are active.
•
The [FWD/REV] key, on the condition that is has
been selected as active in parameter
016 Local
reversing
, and that parameter
013 Local control
is
set at
[1] Local control and open loop
or
[3] Local
control
as
parameter 100
. Parameter
200 Output
frequency range
is set at
[1] Both directions
.
•
Parameter 003 Local reference
where the reference
can be set using the [+] and [-] keys.
•
An external control command that can be
connected to the digital inputs (see parameter
013 Local control
).
NOTICE
The [JOG] and [FWD/REV] keys are located on the LCP
control unit.
003
Local Reference
Value:
Parameter 013 Local control
must be set to
[1]
LOC CTRL/OPEN LOOP
or
[2] LOC+DIG CTRL
:
0 - f
MAX
(parameter 205)
50
Hz
Parameter 013 Local control
must be set to
[3]
LOC CTRL/AS P100
or
[4] LOC+DIG CTRL/AS P100
.
Ref
MIN
- Ref
MAX
(parameter 204-205)
0,0
Function:
In this parameter, the local reference can be set manually.
The unit of the local reference depends on the configu-
ration selected in
parameter 100 Configuration
.
Description of choice:
To protect the local reference, parameter
002 Local/remote
operation
must be set to
[1] Local operation
. Local
reference cannot be set via serial communication.
There is a choice of 4 set-ups (parameter set-ups), which
can be programmed independently of one another. The
active set-up can be selected in
parameter 004 Active Setup
.
When an LCP 2 control unit is connected, the active set-up
number appears in the display under
set-up
. It is also
possible to preset the frequency converter to
Multisetup
, so
that it is possible to shift Setups using the digital inputs or
serial communication. Setup shift can be used in a plant in
which, for example, one Setup is used for daytime
operation and another one for night time operation.
In
parameter 006 Setup copying
it is possible to copy from
one Setup to another. Using
parameter 007 LCP copy
, all
Setups can be transferred from one frequency converter to
another by moving the LCP 2 control panel. First all
parameter values are copied to the LCP 2 control panel,
which can then be moved to another frequency converter.
Here all parameter values can be copied from the LCP 2
control unit to the frequency converter.
Programming
Design Guide
MG27E402
Danfoss A/S © Rev. May/2014 All rights reserved.