7.3 Cooling System Requirements

Table 9: Requirements for Air Cooling

Cooling type

Requirement

Natural convection

Sufficient airflow through inductors, when mounted on top of each other.

Forced air cooling

Nominal airflow 3 m/s.

External fan/blower is required.

Table 10: Requirements for Liquid Cooling

Requirement

Specification

Coolant flow rate

6 l/min

Maximum operating system pressure

6 bar

Maximum pressure

Maximum peak 30 bar/60 s according to UL61800-5-1

Pressure drop (at flow rate 6 l/min)

0.2 bar

Nominal temperature of coolant

5–45 °C

Maximum temperature of coolant

70 °C

Allowed coolants

Drinking water according to 98/83/EY
Demineralized water
Non-corrosive
Propylene glycol or ethylene glycol mixture with the preceding water qualities

Cooling system connections

Following the drive system connections

Cooling system materials

Stainless steel: AISI304, AISI316
Aluminum: Corrosion resistant
Glycol-tolerant plastics

Not allowed:

 Copper, brass, PVC

7.4 Technical Data

Some of the DC filters with rated voltage 750 V DC can be used at nominal 1025 V DC system voltage due to the high impedance
value. See the tables in 

4 Selection

.

Table 11: Technical Data for Air-cooled DC Filters

Code Num-
ber

Filter type code

Manufacturer part
code

Rated
voltage
[V DC]

Cooling Nominal

current
at 50 °C
[A]

Power
loss at
20 °C
[W]

Protec-
tion
rating

Switching
frequency
[kHz]

181B5954

LDC-0010-6-0-APt 40277-SET-PT100

1025

AN

10

60

IP00

5

181B5955

LDC-0010-6-0-ATr 40277-SET-THER-

MIK

181B5956

LDC-0020-5-0-APt 40260-SET-PT100

750

AN

20

110

IP00

5

181B5957

LDC-0020-5-0-ATr 40260-SET-THER-

MIK

181B5958

LDC-0030-6-0-APt 56606-SET-PT100

1025

AN

30

200

IP00

5

AJ377845348678en-000101 / 172F4785

18 | Danfoss A/S © 2023.01

Specifications

DC Filters

Design Guide

Содержание Vacon NXP

Страница 1: ...Design Guide DC Filters VACON NXP DC DC Converter drives danfoss com...

Страница 2: ......

Страница 3: ...ing 7 DC Filter Types 7 Selection 9 Selecting the DC Filter 9 DC Filter Selection Air cooling 9 DC Filter Selection Liquid cooling 11 Installation Guidelines 13 Cabling 13 Thermal Protection 13 Mounti...

Страница 4: ...nd options The VACON NXP DC DC Converter operating guide provides information about the installation and operation of the VACON NXP DC DC Converter application The VACON NXP DC DC Converter applicatio...

Страница 5: ...dous situation which if not avoided will result in death or serious injury W A R N I N G Indicates a hazardous situation which if not avoided could result in death or serious injury C A U T I O N Indi...

Страница 6: ...for lifting purposes C A U T I O N BURN HAZARD FROM HOT SURFACES The filter surface turns hot during operation Wait for the filter to cool down before touching it N O T I C E DAMAGE FROM LOOSE CONNEC...

Страница 7: ...be as high as 1100 V that is 1150 V D input and 50 V DC output Due to the high voltage difference a high inductance value is required to guarantee proper functionality in all operation points The DC f...

Страница 8: ...tion rating 0 IP00 2 IP21 5 IP54 A Cooling method A Natural convection B Forced air cooling C Liquid cooling Pt Temperature measurement type Pt Pt100 temperature sensor Tr Thermal relay X Reserved for...

Страница 9: ...age max current fs 5 kHz Iout nominal A Filter selection Iout max A Filter selection FR4 NXI_0004 5 4 8 LDC 0010 6 0 Axx 8 LDC 0010 6 0 Axx NXI_0009 5 10 18 NXI_0012 5 13 4 24 FR6 NXI_0016 18 LDC 0010...

Страница 10: ...DC fs 5 kHz Low Voltage max current fs 5 kHz Iout nominal A Filter selection Iout max A Filter selection FR6 NXI_0010 6 11 1 LDC 0010 6 0 Axx 14 6 LDC 0010 6 0 Axx NXI_0013 6 14 6 19 NXI_0018 6 20 3...

Страница 11: ...ble 5 DC Filter Selection for Liquid cooled 500 V Drives According to Energy Storage Requirements Drive enclosure size Drive type High Voltage 750 V DC fs 5 kHz Low Voltage max current fs 5 kHz Iout n...

Страница 12: ...ut nominal A Filter selection Iout max A Filter selection CH61 NXP_0170 6 199 LDC 0160 6 0 Cxx 340 LDC 0160 6 0 Cxx NXP_0208 6 244 416 NXP_0261 6 309 500 CH62 NXP_0325 6 385 650 LDC 0340 6 0 Cxx NXP_0...

Страница 13: ...re at the top of the 1 phase inductors and are marked as shown in Illustration 3 10 30 A inductors have terminal connectors 50 1150 A inductors have busbar terminals DC filter terminal sizes and mount...

Страница 14: ...lt signal connected to terminals 3 and 4 1 2 3 4 e30bj645 10 Illustration 5 Terminals for Thermal Protection 5 3 Mounting The DC filter is typically mounted inside a cabinet next to the DC DC converte...

Страница 15: ...ra air baffles and fan In the filter range above 50 A the cooling arrangement must be implemented The cabinet cooling must be guaranteed also with liquid cooled DC filters Typically 30 40 of the power...

Страница 16: ...of the cabinet with care Do not use liquids for the cleaning Tightening torques Check that the tightening torques of the cable connections are according to the specifications See 7 6 Terminal and Torq...

Страница 17: ...2 Environmental Data Table 8 Environmental Data for the DC Filters Item Specification Temperature during operation 10 50 C full performance 50 60 C limited performance Current derating of 2 for each...

Страница 18: ...ctions Following the drive system connections Cooling system materials Stainless steel AISI304 AISI316 Aluminum Corrosion resistant Glycol tolerant plastics Not allowed Copper brass PVC 7 4 Technical...

Страница 19: ...LDC 0170 6 0 APt 37404 SET PT100 1025 AN 170 450 IP00 5 181B5971 LDC 0170 6 0 ATr 37404 SET THER MIK 181B5972 LDC 0270 5 0 APt 38739 SET PT100 750 AN 270 460 IP00 5 181B5973 LDC 0270 5 0 ATr 38739 SE...

Страница 20: ...1150 6 0 CTr 36859 SET THERMIK 7 5 Dimensions The dimensions in Table 13 refer to drawings shown in Illustration 7 Illustration 8 and Illustration 9 Details of the terminal connec tions can be found...

Страница 21: ...C 0420 5 0 APt 308 10 273 10 587 7 252 198 220 11x21 130 LDC 0420 5 0 APt LDC 0540 6 0 BPt 306 10 287 7 560 7 252 198 220 11x21 123 LDC 0540 6 0 BTr LDC 0900 5 0 BPt 276 10 240 5 484 5 186 210 150 11x...

Страница 22: ...tion 7 Dimensions of the Air cooled Inductors 10 30 A A E B D F G C e30bj350 10 Illustration 8 Dimensions of the Air cooled Inductors 30 A AJ377845348678en 000101 172F4785 22 Danfoss A S 2023 01 Speci...

Страница 23: ...LDC 0092 5 0 Axx Busbar 1 x D9 M8 M8 20 20 Base LDC 0092 6 0 Axx Busbar 1 x D9 M8 M8 20 20 Base LDC 0092 5 0 Bxx Busbar 1 x D9 M8 M8 20 20 Base LDC 0170 6 0 Axx Busbar 1 x D11 M10 M10 40 40 Base LDC...

Страница 24: ...l Grounding Terminal Grounding LDC 0340 6 0 Cxx Busbar D 13x20 M12 M10 70 40 Base LDC 0700 6 0 Cxx Busbar D 13x20 M12 M10 70 40 Base LDC 1150 6 0 Cxx Busbar D 13x20 M12 M10 70 40 Base AJ377845348678en...

Страница 25: ...lter types 7 L Liquid cooling 18 M Maintenance 16 Mounting 14 O Overview 7 P Purpose of the manual 4 R Recycling 16 S Safety 5 Selection 9 Specifications 17 Symbols 5 T Technical data 18 Terminals 23...

Страница 26: ...ures and other printed material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subseq...

Отзывы: