5.4.4 Output Signals (Control Panel: Menu M2 -> G2.3)
Table 28: Output Signals, G2.3
Index
Parameter
Min
Max
Unit Default ID
Description
P2.3.1
(1)
Analog output 1 signal selec-
tion
0.1
E.10
-
A.1
464 -
P2.3.2
Analog output function
0
8
-
1
307 0 = Not used (20 mA/10 V)
1 = Output freq. (0–f
max
)
2 = Freq. reference (0–f
max
)
3 = Motor speed (0–Motor nominal speed)
4 = Motor current (0–I
nMotor
)
5 = Motor torque (0–T
nMotor
)
6 = Motor power (0–P
nMotor
)
7 = Motor voltage (0–U
nMotor
)
8 = DC-link volt (0–1000 V)
P2.3.3
Analog output filter time
0.00
10.00
s
1.00
308 0 = No filtering
P2.3.4
Analog output inversion
0
1
-
0
309 0 = Not inverted
1 = Inverted
P2.3.5
Analog output minimum
0
1
-
0
310 0 = 0 mA (0 V)
1 = 4 mA (2 V)
P2.3.6
Analog output scale
10
1000
%
100
311 -
P2.3.7
Digital output 1 function
0
22
-
1
312 0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = AC drive overheat warning
6 = Ext. fault or warning
7 = Ref. fault or warning
8 = Warning
9 = Reversed
10 = Jogging speed selected
11 = At speed
12 = Mot. regulator active
13 = OP freq. limit superv. 1
14 = OP freq. limit superv.2
15 = Torque limit superv.
16 = Ref. limit superv.
17 = Ext. brake control
18 = Control place: I/O
19 = AC drive temp. limit superv.
20 = Unrequested rotation direction
21 = Ext. brake control inverted
22 = Thermistor fault/warn.
P2.3.8
RO1 function
0
22
-
2
313
P2.3.9
RO2 function
0
22
-
3
314
AB296635287482en-000301 / DPD00903
52 | Danfoss A/S © 2023.02
Multi-step Speed Control
Application
VACON® NX All-in-One
Application Guide