100 %
0 %
Min Freq
Max Freq
FB Max
Scale
FB Min
Scale
Frequency
FB Reference input
e
3
0
b
h
1
0
4
.1
0
Illustration 80: Fieldbus Reference Minimum = Maximum Scaling
Using this custom scaling function also affects the scaling of the actual value.
100 %
FB Actual Speed
Min Freq
Max Freq
FB Max
Scale
FB Min
Scale
Output
frequency
e
3
0
b
h
1
0
5
.1
0
Illustration 81: Fieldbus Minimum and Maximum Scaling Effect on Actual Value
10.386 (ID 852) Fieldbus Process Data Out 1 Selection
Location in the menu:
P2.9.3
(Multi-purpose Control Application)
Use this parameter to select the data that is sent to the fieldbus with the ID number of the parameter or monitor value.
To monitor an item, enter the ID number of the item as the value of this parameter.
See
10.624 Fieldbus Control Parameters (IDs 850–859)
ID
Monitoring value
ID
Monitoring value
1
Output frequency
15
Digital inputs 1,2,3 statuses
2
Motor speed
16
Digital inputs 4,5,6 statuses
3
Motor current
17
Digital and relay output statuses
4
Motor torque
25
Frequency reference
5
Motor power
26
Analog output current
6
Motor voltage
27
AI3
AB296635287482en-000301 / DPD00903
264 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide