10.365 (ID 738) Automatic Restart: Number of Tries after Underload Fault Trip
Location in the menu:
P2.8.10
(Standard Application, Local/Remote Control Application, Multi-step Speed Control Application, PID
Control Application, Multi-purpose Control Application, Pump and Fan Control Application)
Use this parameter to enable the automatic reset after an underload fault.
10.366 (ID 739) TBoard1 Numbers (Number of PT100 Inputs in Use)
Location in the menu:
P2.7.24
(PID Control Application, Multi-purpose Control Application, Pump and Fan Control Application)
Use this parameter to select the number of sensors in use when a temperature board is installed.
The parameter name "
TBoard1 Numbers
" is used in Multi-Purpose Control Application. The old name (
Number of PT100 inputs in use
)
is still used in PID Control Application and Pump and Fan Control Application.
If a temperature board is installed in your AC drive, use this parameter to select the number of sensors in use. See also the VACON
®
NX I/O Boards User Manual.
If the selected value is greater than the actual number of used sensors, the display reads 200ºC. If the input is short-circuited, the
shown value is –30ºC.
10.367 (ID 740) TBoard Fault Response (Response to PT100 Fault)
Location in the menu:
P2.7.25
(PID Control Application, Multi-purpose Control Application, Pump and Fan Control Application)
Use this parameter to select the response of the drive to 'Temperature' fault.
The parameter name "
TBoard Fault Response
" is used in Multi-Purpose Control Application. The old name (
Response to PT100 fault
) is
still used in PID Control Application and Pump and Fan Control Application.
10.368 (ID 741) TBoard1 Warning Limit (PT100 Warning Limit)
Location in the menu:
P2.7.26
(PID Control Application, Multi-purpose Control Application, Pump and Fan Control Application)
Use this parameter to set the temperature warning limit.
The parameter name "
TBoard1 Warning Limit
" is used in Multi-Purpose Control Application. The old name (
PT100 warning limit
) is still
used in PID Control Application and Pump and Fan Control Application.
10.369 (ID 742) TBoard1 Fault Limit (PT100 Fault Limit)
Location in the menu:
P2.7.27
(PID Control Application, Multi-purpose Control Application, Pump and Fan Control Application)
Use this parameter to set the temperature fault limit.
The parameter name "
TBoard1 Fault Limit
" is used in Multi-Purpose Control Application. The old name (
PT100 fault limit
) is still used
in PID Control Application and Pump and Fan Control Application.
10.370 (ID 743) TBoard2 Numbers
Location in the menu:
P2.7.37
(Multi-purpose Control Application)
Use this parameter to select the number of sensors in use when a temperature board is installed.
If a temperature board is installed in your AC drive, use this parameter to select the number of sensors in use. See also the VACON
®
NX I/O Boards User Manual.
If the selected value is greater than the actual number of used sensors, the display reads 200ºC. If the input is short-circuited, the
shown value is –30ºC.
10.371 (ID 745) TBoard2 Warning Limit
Location in the menu:
P2.7.38
(Multi-purpose Control Application)
Use this parameter to set the temperature warning limit.
10.372 (ID 746) TBoard2 Fault Limit
Location in the menu:
P2.7.39
(Multi-purpose Control Application)
Use this parameter to set the temperature fault limit.
10.373 (ID 750) Cooling Monitor
Location in the menu:
P2.2.7.23
(Multi-purpose Control Application)
Use this parameter to select the digital input signal that shows the state of the used cooling unit. This parameter is used for liquid-
cooled AC drives.
AB296635287482en-000301 / DPD00903 | 261
Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide