Use this parameter to connect the AI2 signal to the analog input of your selection.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
10.138 (ID 393) AI2 Reference Scaling, Minimum Value
Location in the menu:
P2.2.3.6
(Multi-purpose Control Application)
Use this parameter to set extra reference scaling.
If the values of both
ID 393
and
ID 394
are zero, the scaling is set off. The minimum and maximum frequencies are used for scaling.
See parameters
ID 303
and
ID 304
.
10.139 (ID 394) AI2 Reference Scaling, Maximum Value
Location in the menu:
P2.2.3.7
(Multi-purpose Control Application)
Use this parameter to set extra reference scaling.
If the values of both
ID 393
and
ID 394
are zero, the scaling is set off. The minimum and maximum frequencies are used for scaling.
See parameters
ID 303
and
ID 304
.
10.140 (ID 395) AI2 Joystick Hysteresis
Location in the menu:
P2.2.3.8
(Multi-purpose Control Application)
Use this parameter to set the joystick hysteresis.
This parameter defines the joystick dead zone between 0–20%. See
ID 384
.
10.141 (ID 396) AI2 Sleep Limit
Location in the menu:
P2.2.3.9
(Multi-purpose Control Application)
Use this parameter to set the sleep limit. The AC drive stops automatically if the AI signal level falls below the value set with this
parameter.
See also parameter
ID 397
. See ID 385.
10.142 (ID 397) AI2 Sleep Delay
Location in the menu:
P2.2.3.10
(Multi-purpose Control Application)
Use this parameter to set the time during which the analog input signal must stay under the sleep limit before the AC drive stops.
10.143 (ID 399) Scaling of Current Limit
Location in the menu:
P2.2.6.1
(Multi-purpose Control Application)
Use this parameter to select the signal to adjust the maximum value of the motor current.
For selection 5 "Fieldbus (FB ProcessDataIN2)", see
10.624 Fieldbus Control Parameters (IDs 850–859)
This signal adjusts the maximum motor current between 0 and
Motor current limit
(
ID 107
).
10.144 (ID 400) Scaling of DC-Braking Current
Location in the menu:
P2.2.6.2
(Multi-purpose Control Application)
Use this parameter to select the signal to adjust the DC-braking current.
See parameter
ID 399
for the selections.
DC-braking current can be reduced with the free analog input signal between zero current and the current set with parameter
ID
507
.
AB296635287482en-000301 / DPD00903
214 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide