•
•
•
100%
0
ID304
ID303
ID321
ID322
ID320 = 0
AI1 = 0—100%
f
out
AI1
(term. 2)
ID320 = 1
AI1 = custom
Illustration 44: AI1 Signal Inversion
10.82 (ID 324) AI1 Signal Filter Time
Location in the menu:
P2.2.8
(Local/Remote Control Application, Multi-Step Speed Control Application)
P2.2.20
(PID Control Application)
P2.2.2.2
(Multi-Purpose Control Application, Pump and Fan Control Application)
Use this parameter to filter out disturbances in the analog input signal.
To activate this parameter, give it a value that is bigger than 0.
Long filtering time makes the regulation response slower.
[%]
100%
63%
[s]
ID324
e
3
0
b
h
0
3
8
.1
0
C
A
B
Illustration 45: AI1 Signal Filtering
A
Unfiltered signal
B
Filtered signal
C
Time
10.83 (ID 325) AI2 Signal Range
Location in the menu:
AB296635287482en-000301 / DPD00903
196 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide
Содержание VACON NX
Страница 1: ...Application Guide VACON NX All in One drives danfoss com...
Страница 2: ......