7.4.9 Protections (Control Panel: Menu M2 -> G2.7)
Table 81: Protections, VACON
®
NXS, G2.7
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.7.1
Response to 4 mA reference fault
0
5
-
0
700
0 = No response
1 = Warning
2 = Previous Freq.
3 = Wrng+Preset- Freq 2.7.2
4 = Fault, stop acc. to 2.4.7
5 = Fault, stop by coasting
P2.7.2
4 mA reference fault frequency
0.00
P2.1.2
Hz
0.00
728
-
P2.7.3
Response to external fault
0
3
-
2
701
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
P2.7.4
Input phase supervision
0
3
-
3
730
P2.7.5
Response to undervoltage fault
0
1
-
0
727
0 = Fault stored in history
1 = Fault not stored
P2.7.6
Output phase supervision
0
3
-
2
702
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
P2.7.7
Earth fault protection
0
3
-
2
703
P2.7.8
Thermal protection of the motor
0
3
-
2
704
P2.7.9
Motor ambient temperature factor
-100.0
100.0
%
0.0
705
-
P2.7.10
Motor cooling factor at zero speed
0.0
150.0
%
40.0
706
-
P2.7.11
Motor thermal time constant
1
200
min
Varies
707
-
P2.7.12
Motor duty cycle
0
150
%
100
708
-
P2.7.13
Stall protection
0
3
-
0
709
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
P2.7.14
Stall current
0.00
P2.1.2
A
I
H
710
-
P2.7.15
Stall time limit
1.00
120.00
s
15.00
711
-
P2.7.16
Stall frequency limit
1.0
P2.1.2
Hz
25.00
712
-
P2.7.17
Underload protection
0
3
-
0
713
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
P2.7.18
Field weakening area load
10.0
150.0
%
50.0
714
-
AB296635287482en-000301 / DPD00903 | 113
Danfoss A/S © 2023.02
Multi-purpose Control Application
VACON® NX All-in-One
Application Guide