8.
1.
-
-
-
-
-
-
Do a check of the quality and quantity of the cooling air.
Before connecting the drive to the mains, do a check of the installation and the condition of all the protective devices.
Collect all the necessary device instruction manuals, drawings, and materials, and save them.
8.4 Commissioning Report
After the commissioning is finished, the user and the commissioning engineer from Danfoss must accept and sign the commission-
ing report. The Danfoss commissioning engineer must write two duplicate commissioning reports, one copy is for the user and the
other for Danfoss.
8.5 Operating the Drive
8.5.1 Powering the Drive
Only personnel who have been trained professionally can operate the VACON® 1000 medium-voltage drive.
Procedure
Switch on the auxiliary control supply.
Input the correct password to the HMI.
Set and check the system function and start-up parameters.
See the VACON® 1000 Application Guide.
C A U T I O N
To ensure the safety and normal operation of the drive, the important parameters must be confirmed carefully.
Close all cabinet doors.
All the cabinet doors must be closed reliably, otherwise the drive does not start.
If a bypass cabinet is configured, check the main circuit configuration.
Close the input isolation switch.
Close the output isolation switch.
Live operation of the knife gate isolation switch is prohibited.
Check that the VACON® 1000 is ready.
The HMI display is normal, and no failure warning information is shown.
If a warning is shown, see
.
The “MCB close allowed” indicator in the VACON® 1000 status interface blinks.
Close the high voltage breaker.
The “MCB closed” indicator in the VACON® 1000 status interface blinks.
The VACON® 1000 is ready, and the “Start-up ready” indicator in the status interface blinks.
8.5.2 Starting the Drive
The steps for starting the VACON® 1000 depend on the operation mode and reference mode.
Make sure that it is safe to start the motor.
Procedure
Set the speed.
HMI
: Input the reference speed in the HMI.
Analog
: Input the speed setting through the analog input.
Digital
: Input the speed setting through DCS digital signal.
Communication
: Input the speed setting through communication.
PID
: Input PID reference value.
AQ363633621020en-000201 / 172F3117
76 | Danfoss A/S © 2021.06
Commissioning
VACON® 1000
Operating Guide