Enclo-
sure
size
Drive Type
I
L
[A]
Fuse
(gG/g
L) [A]
Mains, motor, and brake resistor
(1)
cable Cu [mm
2
]
Mains terminal cable size
[mm
2
]
Grounding
terminal ca-
ble size
[mm
2
]
MR9B
0262 6
0262 7
261.0
315
3x185+95
2x(3x95+29)
Bolt size M10
Bolt size M8
1
If you use a multi-conductor cable, 1 of the conductors of the brake resistor cable stays unconnected. It is also possible to use a single cable if you obey the minimum cross- sectional
area of the cable.
10.3.4 Cable and Fuse Sizes, Mains Voltage 208–240 V and 380–500 V, North America
Table 26: Cable and Fuse Sizes, Mains Voltage 208–240 V and 380–500 V, North America
Enclosure
size
Drive type
I
L
[A]
Fuse
(Class T/J)
[A]
Mains, motor and
brake resistor
(1)
ca-
ble Cu [AWG]
Mains terminal cable size
[AWG]
Grounding terminal
cable size [AWG]
MR4
0003 2
0003 5
3.7
3.4
6
14
24–10
17–10
0004 2
0004 5
4.8
6
14
24–10
17–10
0006 2
0005 5
6.6
5.6
10
14
24–10
17–10
0008 2
0008 5
8.0
10
14
24–10
17–10
0011 2
0009 5
11.0
9.6
15
14
24–10
17–10
0012 2
0012 5
12.5
12.0
20
14
24–10
17–10
MR5
0018 2
0016 5
18.0
16.0
25
10
20–6
17–8
0024 2
0023 5
24.0
23.0
30
10
20–6
17–8
0031 2
0031 5
31.0
40
8
20–6
17–8
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711| 109
Danfoss A/S © 2019.05