Operating Guide
Termix VVX Compact 28/18 – 7 Series BS-HC
7.0 Troubleshooting
7.1 Troubleshooting in general
In the event of operating disturbances, the following basic features
should be checked before carrying out actual troubleshooting:
•
the substation is connected to electricity,
•
the strainer on the DH supply pipe is clean,
•
the supply temperature of the DH is at the normal level
(summer, at least 60 °C - winter, at least 70 °C),
•
the differential pressure is equal to or higher than the normal
(local) differential pressure in the DH network – if in doubt, ask
the DH plant supervisor,
•
pressure on the system - check the HE pressure gauge.
Authorized personnel only
Assembly, start-up and maintenance work must be performed by
qualified and authorized personnel only.
7.2 Troubleshooting DHW
Problem
Possible cause
Solution
Insufficient credit on the pre-payment unit,
if installed.
Top up your credit.
Strainer in supply or return line clogged.
Clean strainer(s).
DHW circulation pump out of order or with
too low setting.
Check circulation pump.
Defective or clogged non-return valve.
Replace – clean.
No electricity.
Check.
Wrong setting of automatic controls, if any.
To adjust an electronic controller for
DHW, pls. note enclosed instructions for
electronic controller.
Scaling of the plate heat exchanger.
Replace – rinse out.
Defective motorized valve.
Check (use manual function) – replace.
Defective temperature sensors.
Check – replace.
Too little or no DHW.
Defective controller.
Check – replace.
DCW is being mixed with the DHW, e.g. in
a defective thermostatic mixing valve.
Check – replace.
Hot water in some taps but not in all.
Defective or clogged non-return valve on
circulation valve.
Replace – clean.
Tap temperature too high; DHW tap load
too high.
Thermostatic valve adjusted to a too high
level.
Check – set.
Scaling of the plate heat exchanger.
Replace – rinse out.
Temperature drop during tapping.
Larger DHW flow than the substation has
been designed for.
Reduce DHW flow.
Thermostatic control valve does not close
Temperature difference between DH
supply and DHW set point too low.
Lower the set point temperature or
increase the DH supply temperature.
LGB42404
DEN-GT
21
Содержание Termix VVX Compact 28/18 - 7 BS-HC Series
Страница 24: ...Operating Guide Termix VVX Compact 28 18 7 Series BS HC 24 DEN GT LGB42404...
Страница 25: ...Operating Guide Termix VVX Compact 28 18 7 Series BS HC LGB42404 DEN GT 25...
Страница 26: ...Operating Guide Termix VVX Compact 28 18 7 Series BS HC 26 DEN GT LGB42404...
Страница 28: ...Operating Guide Termix VVX Compact 28 18 7 Series BS HC Produced by Gemina Termix A S 04 2018...